Plan Review Notes For Permit 01121717 |
Permit Number |
01121717 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-01-07 00:00:00 | *************** UNSAT **************** | | | | 1)NOTE: PLEASE NOTE THAT PLANS FOR | | # 01090788 SHOW A HEAT PUMP AT 11KW | | BEING IN LOAD CALCULATIONS. | | | | 2)NOTE: PLEASE NOTE THAT WIRING DIAGRAM | | ON THESE PLANS DO NOT INCLUDE ANY | | HEAT PUMP OR ASSC. WIRING? | | PLEASE SHOW, INCLUDE, WIRE SIZE, CONDUIT | | ETC. PLEASE CLARIFY HEAT PUMP SIZE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|