Plan Review Notes
Plan Review Notes For Permit 01121466
Permit Number 01121466
Review Stop E
Sequence Number 1
Notes
Date Text
2002-01-15 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER 220-3-C-1 FOR MORETHAN 500SQ FT.
 PLEASE NOTE THAT A NEW ELECTRICAL PANEL
 IS SHOWN IN NEW ADDITION, BUT NO RISER
 DIAGRAM WAS SUBMITTED FOR REVIEW.
 PLEASE SUBMIT A RISER DIAGRAM SHOWING
 WHERE/HOW THIS PANEL IS BEING FED.
 WIRE SIZES/CONDUIT ECT.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 PLEASE SUBMIT A PANEL SCHEDULE SHOWING
 EXSITING? NEW? CIRCUITS, REQ`D.
  
 3)NOTE: PLEASE NOTE THAT MORETHAN 50% OF
 THE ELECTRICAL IS BEING DONE, NOTE SD`S
 WILL BE REQ`D INSIDE AND OUTSIDE ANY
 EXISTING BEDROOMS. PLEASE SHOW
 PLEASE NOTE SD REQ`D IN CABANA, THIS
 ROOM HAS CLOSET/STORAGE AND IS
 CONSIDERED AN ADAPTABLE BEDROOM. NFPA-72
 2-1.1.1
  
 4)NOTE: PLEASE NOTE THAT IF ANY NEW
 ELECTRICAL SERVICE IS GOING TO BE
 SUBMITTED FOR REVIEW, PLEASE SUBMIT THE
 AIC RATINGS FOR ANY NEW SERVICE. 110-9
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372