2002-01-15 00:00:00 | ******************* UNSAT ************** |
| |
| 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| PER 220-3-C-1 FOR MORETHAN 500SQ FT. |
| PLEASE NOTE THAT A NEW ELECTRICAL PANEL |
| IS SHOWN IN NEW ADDITION, BUT NO RISER |
| DIAGRAM WAS SUBMITTED FOR REVIEW. |
| PLEASE SUBMIT A RISER DIAGRAM SHOWING |
| WHERE/HOW THIS PANEL IS BEING FED. |
| WIRE SIZES/CONDUIT ECT. |
| |
| 2) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| PLEASE SUBMIT A PANEL SCHEDULE SHOWING |
| EXSITING? NEW? CIRCUITS, REQ`D. |
| |
| 3)NOTE: PLEASE NOTE THAT MORETHAN 50% OF |
| THE ELECTRICAL IS BEING DONE, NOTE SD`S |
| WILL BE REQ`D INSIDE AND OUTSIDE ANY |
| EXISTING BEDROOMS. PLEASE SHOW |
| PLEASE NOTE SD REQ`D IN CABANA, THIS |
| ROOM HAS CLOSET/STORAGE AND IS |
| CONSIDERED AN ADAPTABLE BEDROOM. NFPA-72 |
| 2-1.1.1 |
| |
| 4)NOTE: PLEASE NOTE THAT IF ANY NEW |
| ELECTRICAL SERVICE IS GOING TO BE |
| SUBMITTED FOR REVIEW, PLEASE SUBMIT THE |
| AIC RATINGS FOR ANY NEW SERVICE. 110-9 |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW, IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |