Plan Review Notes For Permit 01121416 |
Permit Number |
01121416 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-12-24 00:00:00 | 1) PLEASE PROVIDE AN A.I.C.RATING FOR | | MAIN BREAKER. | | 2)PLAN SHOWS NO STAIRWELL LIGHTING, | | PLEASE CLARIFY.210-70A | | 3)MUST HAVE OUTDOOR G.F.I'S.210-52C | | 4)THE LOAD CALC'S DON'T SHOW THE | | REQUIRED LAUNDRY CIRCUITS AS PER | | 210-52F5)THE SMOKE DETECTORS ARE SHOWN | | INERCONNECTED FROM THE UPPER AND LOWER | | UNITS,PLEASE CLARIFY. | | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | (561) 659-8096 EXT 8392. |
|