Plan Review Notes
Plan Review Notes For Permit 01121259
Permit Number 01121259
Review Stop E
Sequence Number 3
Notes
Date Text
2002-05-16 00:00:00*************** UNSAT ***************
  
 1 )NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
 PLEASE SHOW TRACK LIGHTING PER 220-12B
 PLEASE ALSO NOTE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%.
  
 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS AND CORRELATE WITH PANEL
 SCHEDULES SUBMITTED. USE HAS CHANGED .
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-806 EXT 8372