Plan Review Notes For Permit 01121259 |
Permit Number |
01121259 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-01-12 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) EXISTING FLOOR PLAN REQUIRED TO SEE | | WHAT IS CHANGED. | | 2) NEW LAUNDRY FLOOR DRAIN. PLEASE GIVE | | DETAILS FOR AREA. SHOW HOW THE FLOOR | | WILL BE SEALED IN AREA OF DRAIN. FLOOR | | DRAIN SHALL HAVE A TRAP PRIMER. | | 3) PLEASE INDICATE WHAT THE COMMERCIAL | | SINKS WILL BE USED FOR. | | 4) SANITARY RISER DIAGRAM REQUIRED FOR | | FLOOR DRAIN TO SHOW HOW IT IS TIED INTO | | EXISTING SYSTEM. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|