Plan Review Notes
Plan Review Notes For Permit 01121255
Permit Number 01121255
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-12-20 00:00:001) NO SMOKE DETECTORS OBSERVED IN
 ELEVATOR LOBBIES ON THE SIXTH AND
 SEVENTH FLOORS.
 2) PLEASE INDICATE ON THE PLANS WHAT
 THE VOICE EVACUATION PORTION OF THE
 FIRE ALARM SYSTEM WILL ADVISE PERSONS
 TO DO IN THE EVENT OF AN EMERGENCY.
 3) NO MANUAL PULL STATIONS SHOWN ON
 THE PLANS FOR THE UPPER FLOORS OF
 THE BUILDING.
 4) NO MANUAL PULL STATIONS NEAR STAIRS
 2 AND 3 IN THE GARAGE AREA.
 5) NO SMOKE DETECTOR PROVIDED ABOVE
 FIRE ALARM CONTROL PANELS.
 6) PLEASE EXPLAIN RATIONALE FOR SMOKE
 DETECTORS IN THE LAUNDRIES AND THE
 TRASH ROOMS.
 7) PLEASE INDICATE ON THE PLANS FIRE
 PUMP RUN, FIRE PUMP FAIL, AND PHASE
 REVERSAL.
 8) THE FIRE ALARM SYSTEM IS TO BE
 MONITORED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED BY THE FIRE
 RESCUE DEPARTMENT.
 9) DUCT SMOKE DETECTORS REQUIRED IN
 HVAC UNITS OVER 2000 CFM.
 10) ADDITIONAL FIRE ALARM EQUIPMENT
 WILL BE REQUIRED IN THE FUTURE RETAIL
 SPACES OF THE BUILDING.
 11) PLEASE INDICATE ON THE PLANS WHAT
 AREAS OF THE BUILDING WILL GO INTO
 GENERAL ALARM MODE. WILL IT BE THE
 ENTIRE BUILDING OR CERTAIN AREAS OF
 THE BUILDING.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910