2001-12-20 00:00:00 | 1) NO SMOKE DETECTORS OBSERVED IN |
| ELEVATOR LOBBIES ON THE SIXTH AND |
| SEVENTH FLOORS. |
| 2) PLEASE INDICATE ON THE PLANS WHAT |
| THE VOICE EVACUATION PORTION OF THE |
| FIRE ALARM SYSTEM WILL ADVISE PERSONS |
| TO DO IN THE EVENT OF AN EMERGENCY. |
| 3) NO MANUAL PULL STATIONS SHOWN ON |
| THE PLANS FOR THE UPPER FLOORS OF |
| THE BUILDING. |
| 4) NO MANUAL PULL STATIONS NEAR STAIRS |
| 2 AND 3 IN THE GARAGE AREA. |
| 5) NO SMOKE DETECTOR PROVIDED ABOVE |
| FIRE ALARM CONTROL PANELS. |
| 6) PLEASE EXPLAIN RATIONALE FOR SMOKE |
| DETECTORS IN THE LAUNDRIES AND THE |
| TRASH ROOMS. |
| 7) PLEASE INDICATE ON THE PLANS FIRE |
| PUMP RUN, FIRE PUMP FAIL, AND PHASE |
| REVERSAL. |
| 8) THE FIRE ALARM SYSTEM IS TO BE |
| MONITORED BY A LICENSED UL LISTED |
| CENTRAL STATION APPROVED BY THE FIRE |
| RESCUE DEPARTMENT. |
| 9) DUCT SMOKE DETECTORS REQUIRED IN |
| HVAC UNITS OVER 2000 CFM. |
| 10) ADDITIONAL FIRE ALARM EQUIPMENT |
| WILL BE REQUIRED IN THE FUTURE RETAIL |
| SPACES OF THE BUILDING. |
| 11) PLEASE INDICATE ON THE PLANS WHAT |
| AREAS OF THE BUILDING WILL GO INTO |
| GENERAL ALARM MODE. WILL IT BE THE |
| ENTIRE BUILDING OR CERTAIN AREAS OF |
| THE BUILDING. |
| |