Plan Review Notes For Permit 01121251 |
Permit Number |
01121251 |
|
Review Stop |
R |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-03-26 00:00:00 | REVISION CHECKLIST: | | 1-CHANGE OF USE FROM GARAGE TO SALES | | OFFICE NEEDS TO COMPLY WITH FLORIDA | | ACCESSIBILITY CODE FOR BUILDING CONST. | | 1997 ED. PROVIDE ACCESSIBLE ROUTE, | | ACCESSIBLE RESTROOM AND ACCESSIBLE | | PARKING. | | 2-PROVIDE COMPLETE SPECIFICATIONS AND | | INSTALLATION DETAILS FOR AWNNG OR | | APPLY FOR A SEPARATE PERMIT. | | 3-CLEARLY SPECIFY ON PLANS SAFETY GLASS | | REQUIRED BY SECTION 2405.2 SBC 1997. | | 4-PRODUCT APPROVAL SUBMITTED FOR ENTRY | | DOORS IS FOR OUTSWING DOOR. DRAWINGS | | SHOW INSWING DOOR. REVISE AS REQUIRED. | | 5-VALUE FOR BUILDING SALES OFFICE NEEDS | | TO BE DECLARED TO APPLY PROPER FEES. | | 6-PROVIDE COMPLETE INFORMATION FOR STORM | | SHUTTERS OR APPLY FOR SEPARATE PERMIT. |
|