2002-03-26 00:00:00REVISION CHECKLIST:
 1-CHANGE OF USE FROM GARAGE TO SALES
 OFFICE NEEDS TO COMPLY WITH FLORIDA
 ACCESSIBILITY CODE FOR BUILDING CONST.
 1997 ED. PROVIDE ACCESSIBLE ROUTE,
 ACCESSIBLE RESTROOM AND ACCESSIBLE
 PARKING.
 2-PROVIDE COMPLETE SPECIFICATIONS AND
 INSTALLATION DETAILS FOR AWNNG OR
 APPLY FOR A SEPARATE PERMIT.
 3-CLEARLY SPECIFY ON PLANS SAFETY GLASS
 REQUIRED BY SECTION 2405.2 SBC 1997.
 4-PRODUCT APPROVAL SUBMITTED FOR ENTRY
 DOORS IS FOR OUTSWING DOOR. DRAWINGS
 SHOW INSWING DOOR. REVISE AS REQUIRED.
 5-VALUE FOR BUILDING SALES OFFICE NEEDS
 TO BE DECLARED TO APPLY PROPER FEES.
 6-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS OR APPLY FOR SEPARATE PERMIT.