Plan Review Notes For Permit 01121251 |
Permit Number |
01121251 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-03-06 00:00:00 | APPROVED WITH PROVISO: | | 1-STORM SHUTTERS: SINCE INFORMATION IS | | NOT CORRECT AND INCOMPLETE, THEN APPLY | | FOR STORM SHUTTERS UNDER A SEPARATE | | PERMIT TO EXPEDITE BUILDING PERMIT. | | 2-SPECIFY FASTENERS FOR GUARDRAILS THAT | | SATISFY THE DESIGN REQUIREMENTS OF | | SEC. 1608.2.2 SBC 1997. DETAIL GIVEN | | AT BOTTOM OF PAGE 4 OF 7 IS ONLY FOR | | THE RAILING PART, NOT THE GUARDRAIL. | | 3-PROVIDE PRODUCT APPROVAL FOR: | | A)SINGLE HUNG WINDOWS (NEED ACTUAL | | PRODUCT APPROVAL, NOT TESTING RESULTS) | | B)DOUBLE ENTRY DOORS (THE ONE SUBMITTED | | IS FOR SINGLE DOORS ONLY). | | C)SLIDING GLASS DOORS. SEE SIZES AND | | DESIGN PRESSURES SHOWN ON THE PLANS. | | MAKE SURE ALL DRAWINGS ARE LEGIBLE. | | D)ARCHED WINDOWS (FIXED WINDOW PRODUCT | | APPROVAL IS FOR RECTANGULAR WINDOWS | | ONLY. SEE PRODUCT APPROVAL DRAWINGS | | FOR APPROVED SIZE AND SHAPES. | | E)WINDOW MULLIONS. | | F)AWNING WINDOW. (DWGS ARE NOT LEGIBLE). | | | | 4-SEE COMMENTS ON PLANS |
|