Plan Review Notes
Plan Review Notes For Permit 01121251
Permit Number 01121251
Review Stop R
Sequence Number 1
Notes
Date Text
2002-01-29 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PAY IMPACT FEES AND BRING PAID RECEIPT
 3-CLARIFY LOCATION OF SHEARWALL SEGMENTS
 AND DIMENSIONS. SEE ELEVATIONS AND
 2ND. FLOOR FRAMING PLAN.
 -CLARIFY FASTENING AT ENDS OF SHEARWALL
 -CLARIFY WHY THERE ARE NOT SHEARWALLS
 AT FRONT ELEVATION?
 -HOW ARE CORNERS AT 2ND FL. REINFORCED?
 4-FIRST FLOOR BATH TO HAVE DOOR THAT
 PROVIDES 29" MIN. CLEAR OPENING. SEC.
 11 OF FLORIDA ACCESSIBILITY CODE, 1997
 5-PROVIDE ATTIC ACCESS AT LANAI ROOF.
 SEC. 2309.6 SBC 1997.
 6-SHOW RAILINGS AT STAIRS. SEC. 1007.5
 -SPECIFY FASTENERS FOR GUARDRAILS AND
 HANDRAILS THAT SATISFY THE DESIGN
 REQUIREMENTS OF SEC. 1608.2 SBC 1997.
 7-SPECIFY BEAM ABOVE BREAKFAST AREA AND
 END CONNECTORS. SEC. 104.2.2 CITY
 AMENDMENTS AND SEC. 1606 SBC 1997.
 8-COMPLETE STEEL COLUMN DETAIL. SPECIFY
 TOP AND BOTTOM ATTACHMENTS. SECTION
 104.2.2 CITY AMENDMENTS TO SBC 1997 &
 SEC. 1606 SBC 1997.
 9-PROVIDE STRUCTURAL BUCK DETAIL FOR
 EXTERIOR SWING DOORS. SEC. 104.2.2
 CITY AMENDMENTS TO SBC 1997.
 10-SOIL TEST REPORT TO HAVE ENGINEER'S
 ORIGINAL SIGNATURE (NOT RUBBER STAMP)
 AS REQUIRED BY CHAPTER 471 FL STATUTES
 11-LEFT SIDE EXTERIOR ELEVATION DOESN'T
 MATCH FLOOR PLANS. SEE WINDOWS AND
 DOORS NOT SHOWN.
 -CLARIFY PITCH OF ROOF. SEE ELEVATIONS.
 12-PROVIDE PRODUCT APPROVAL FOR:
 A)ENTRY DOORS.
 B)HORIZONTAL ROLLING WINDOWS (DRAWINGS
 ARE NOT LEGIBLE).
 C)SINGLE HUNG WINDOWS.
 D)SLIDING GLASS DOORS(DWGS NOT LEGIBLE).
 E)ARCHED WINDOWS. SEE SIZES ON PLANS.
 F)WINDOW MULLIONS.
 G)AWNING WINDOWS.
 H)ROOF TILE.
  
 13-SPECIFY THE DESIGN PRESSURES THAT
 WERE CALCULATED AT EACH EXT. OPENING.
 SEC. 1606 SBC 1997.
 14-REVISE THE OWNER INFORMATION IN THE
 ENERGY CALCULATIONS AND COMPLETE ALL
 INFORMATION ON TOP OF FORM.
 15-SPECIFY FASTENINGS FOR RAILINGS AND
 GUARDRAILS TO COMPLY WITH SECTION
 1608.2 SBC 1997.
 -SHOW RAILINGS ON PLANS. SECTION
 1007.5 SBC 1997.
 16-SPECIFY CEILING INSTALLATION AT ENTRY
 AND REAR PORCHES. SEE ASTM C926 AND
 ASTM C1063 FOR PROPER SPECIFICATIONS.
 SEC. 2504.2SBC 1997.
 17-SEE COMMENTS ON PLANS, INCLUDING
 COMMENTS BY THE OTHER TRADES.
 -PLEASE BRING BACK REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.
 18-STORM PANELS:
 A)PROVIDE COMPLETE INSTALLATION SCHEDULE
 AS PER CITY SAMPLE ATTACHED.
 B)PROVIDE KEY PLAN THAT MATCHES ACTUAL
 ARCHITECTURAL PLANS.
 C)STORM SHUTTERS PRODUCT APPROVAL IS
 GOOD FOR ONE PERMIT ONLY. SEE NOTE ON
 STORM SHUTTERS APPROVED DRAWINGS.
 D)CLEARLY INDICATE ON STORM SHUTTER DWGS
 THE SPECIFIC MOUNTING CONDITIONS AND
 ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE MEAN ROOF HEIGHT,
 DESIGN PRESSURES, PANEL SPAN, EDGE
 DISTANCE AND STRUCTURE TO BE ATTACHED
 TO (WOOD OR CONCRETE BLOCK).