Plan Review Notes
Plan Review Notes For Permit 01121248
Permit Number 01121248
Review Stop R
Sequence Number 3
Notes
Date Text
2002-04-18 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-ARCHITECT TO REVIEW ALL TRUSS DRAWINGS
 AFTER CORRECTIONS ARE DONE.
 2-TRUSS LAYOUT:
 A)ENGINEER TO PROVIDE HIS INFORMATION AS
 REQ'D BY CHAPTER 471 FLORIDA STATUTES.
 B)REVISE LOADING CRITERIA. SEE THE
 STRUCTURAL DRAWINGS.
 C)SPECIFY CODE AND YEAR USED.
 3-ENGINEERED TRUSSES:
 A)REVISE LOADING CRITERIA FOR FLOOR
 TRUSSES AND ROOF TRUSSES. SEE THE
 STRUCTURAL DRAWINGS.
 B)CLEARLY SPECIFY CODE USED & YEAR.
 SBC 1999 IS NOT THE CODE ADOPTED BY
 THE CITY OF WEST PALM BEACH.
 C)TRUSS ENGINEER TO PROVIDE DRAWINGS W/
 ORIGINAL SIGNATURE. CHAPTER 471 FL. ST
 4-ARCHITECT'S ANCHOR SCHEDULE:
 A)THERE IS NOT RT24T CONNECTOR ON USP
 CATALOGUE. IS THIS A CUSTOM MADE
 CONNECTOR?. PROVIDE SPECIFICATIONS AND
 ENGINEERED CALCULATIONS.
 B)SAME COMMENTS AS ABOVE FOR CONNECTOR
 HTA48.
 C)CONNECTOR #9 DOESN'T RESIST THE UPLIFT
 LOADS CALCULATED ON THE ENGINEERED
 ROOF TRUSSES. REVISE AS REQUIRED. SEE
 ENGINEERED TRUSSES.
 5-PROVIDE COMPLETE DETAILS AND SPECS FOR
 INTERMEDIATE COLUMNS TO SUPPORT TRUSS
 H1A. SPECIFY ALL CONNECTORS, TOP AND
 BOTTOM AND FOOTING SIZE & REINFORCING.