Date |
Text |
2002-03-07 00:00:00 | APPROVED WITH PROVISO: |
| 1-PROVIDE CORRECT INFORMATION FOR STORM |
| PANELS UNDER A SEPARATE PERMIT. |
| CHECK ANCHOR TYPE AND SPACING FOR |
| MASONRY NOT CONCRETE. SEE LIMITATIONS |
| ON PRODUCT APPROVAL. |
| 2-SPECIFY ALL FASTENERS FOR GUARDRAILS |
| TO SATISFY DESIGN REQUIREMENTS OF SEC |
| 1608.2.2 SBC 1997. |
| 3-PROVIDE PRODUCT APPROVAL FOR: |
| A)SINGLE HUNG WINDOWS (NEED ACTUAL |
| PRODUCT APPROVAL, NOT JUST TEST RESULT |
| B)DOUBLE ENTRY DOORS AS SHOWN ON PLANS. |
| C)SLIDING GLASS DOORS. SEE SIZES AND |
| DESIGN PRESSURES SHOWN ON PLANS. |
| D)ARCHED WINDOWS. PRODUCT APPROVAL SUB- |
| MITTED IS FOR RECTANGULAR WINDOWS ONLY |
| SEE APPROVED DRAWINGS. |
| E)OVAL WINDOW. SAME COMMENT AS ABOVE. |
| F)WINDOW MULLIONS. |
| G)AWNING WINDOWS. DWGS ARE NOT LEGIBLE. |
| H)SLIDING GLASS DOORS WITH POCKET |
| ASSEMBLY AS SHOWN ON PLANS. |
| I)COMPLETE BUTT GLAZING ASSEMBLY AS |
| SHOWN ON PLANS. IF USING SITE SPECIFIC |
| FORM, THEN IT HAS TO BE SIGNED, SEALED |
| AND DATED BY THE MANUFACTURER'S ENG'R |
| AND BY THE ARCHITECT OF RECORD. SEE |
| ATTACHED SAMPLE. |
| |
| 4-SHEARWALLS LETTER BY ENGINEER NEEDS: |
| A)ORIGINAL SIGNATURE AND DATE. |
| B)ENGINEER NAME AND LICENSE #. |
| ALL THIS INFORMATION IS REQUIRED BY |
| CHAPTER 471 OF FLORIDA STATUTES WHEN |
| SUBMITTING DOCUMENTS FOR PUBLIC |
| RECORDS. |
| C)PROVIDE CORRECT ADDRESS FOR THE CITY |
| OF WEST PALM BEACH BUILDING DEPT. |
| |
| 5-SEE COMMENTS ON PLANS. |
| 6-REVISE AREA TABULATIONS. SEE TOTAL. |
| 7-SPECIFY ON DRAWINGS GLASS AREAS TO |
| HAVE SAFETY GLASS. SEE PLANS AND SEC. |
| 2405.2 SBC 1997. |
| 8-PROVIDE COMPLETE FRAMING DETAIL/SPECS |
| FOR SLIDING GLASS DOORS WITH POCKET |
| BY FAMILY AREA. SEC. 104.2.2 CITY |
| AMENDMENTS AND SEC. 1606 SBC 1997. |
| 9-SPECIFY ALL FASTENERS FOR GUARDRAIL |
| CONSTRUCTION. SEC. 1608.2.2 SBC 1997 |
| 10-SEE GARAGE DOOR PRODUCT APPROVAL FOR |
| STRUCTURAL BUCK INSTALLATION RECOMMEN- |
| DATIONS. |