2002-01-26 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-BRING COPY OF PAID IMPACT FEES RECEIPT
 3-CLARIFY SHEARWALLS:
 A)WHY THERE ARE TWO SHEARWALL SEGMENTS
 SHOWN ON RIGHT ELEVATION ONLY. WHAT
 ABOUT SHEARWALLS ON OTHER ELEVATIONS?
 B)HOW ARE CORNERS AT 2ND FL. REINFORCED?
 4-SPECIFY NUMBER OF RIDGE VENTS ACCORD'G
 TO CALCULATIONS DONE TO DETERMINE THE
 VENTILATION REQUIRED BY SEC. 2309.7
 SBC 1997. THIS IS PART OF THE DESIGN
 SPECIFICATIONS.
 5-SPECIFY THE DESIGN PRESSURES THAT WERE
 CALCULATED AT EACH EXTERIOR OPENINGS
 AS REQUIRED BY SEC. 1606 SBC 1997.
 6-AIR CONDITIONED SQUARE FOOTAGE IS
 INCORRECT:
 A)REVISE CALCULATIONS ON SHEET 2 OF 9.
 B)GO TO PBC AND REVISE SQUARE FOOTAGE
 FOR IMPACT FEES PURPOSE AS WELL.
 C)CONSTRUCTION VALUE WILL BE ADJUSTED
 WHEN PROVIDING CORRECT SQUARE FOOTAGE.
 7-SPECIFY/INDICATE ON PLANS WINDOWS TO
 HAVE SAFETY GLASS. SEC. 2305.2 SBC/97.
 8-PROVIDE COMPLETE FRAMING DETAIL/SPECS
 FOR SLIDING GLASS DOORS WITH POCKET BY
 FAMILY AREA. SEC. 104.2.2 CITY AMENDM.
 9-PROVIDE ATTIC ACCESS AT FIRST FLOOR BY
 BEDROOM #2 REAR ROOF. SEC. 2309.6 SBC
 -PROVIDE ATTIC ACCESS AT 2ND FL. ROOF.
 10-PROVIDE EGRESS WINDOW FOR "GAME ROOM"
 SEC. 1005.4 SBC 1997. FOR SAFETY
 REASONS THIS ROOM IS CONSIDERED FOR
 SLEEPING AS WELL.
 11-SPECIFY FASTENINGS FOR RAILINGS. SEC.
 1608.2 SBC 1997.
 12-REVISE RATIO OF STAIRS TO COMPLY WITH
 SEC. 1007.3 SBC 1997. SEE COMMENTS ON
 STAIR SECTIONS. SHEET 4 OF 9.
 13-PROVIDE COMPLETE WALL SECTIONS THRU
 INTERIOR BEARING WALL BY FAMILY ROOM.
 SEE COMMENTS ON SHEET 4 OF 9.
 SECTION 104.2.2 CITY AMENDMENTS TO SBC
 SAME APPLIES TO INT. WALL SECTION AT
 FRONT AREA.
 14-LAUNDRY ROOM UNDER STAIRS TO COMPLY
 WITH HEADROOM REQUIREMENTS OF SECTION
 1203.2 SBC 1997.
 15-ENG'R TO PROVIDE ORIGINAL SIGNATURE
 ON SOIL TEST REPORT AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 16-CLARIFY REINFORCEMENT FOR ENTRY COLS.
 FOUNDATION PLANS AND SECTION DETAILS
 DON'T MATCH.
 17-CLARIFY DETAIL 4 OF SHEET 8 OF 9. SEE
 COMMENTS ON PLANS.
 18-ROOF FRAMING PLAN ON SHEET 9 OF 9 IS
 VERY CONFUSING BECAUSE IT'S MIXING
 1ST AND SECOND FLOOR. ALSO, IT DOESN'T
 MATCH EXTERIOR ELEVATIONS. REVISE.
 19-PROVIDE STRUCTURAL BUCK DETAIL FOR
 EXTERIOR SWING DOORS. SEC. 104.2.2
 CITY AMENDMENTS AND SEC. 1606 SBC 1997
 20-SPECIFY CEILING INSTALLATION AT ENTRY
 AND REAR PORCHES. SEE ASTM C926 AND
 ASTM C1063 FOR PROPER SPECIFICATIONS.
 SECTION 2504.2 SBC 1997.
 21-SEE COMMENTS ON PLANS. INCLUDING
 THOSE BY THE OTHER TRADES.PLEASE BRING
 BACK REVIEWED SET AFTER CORRECTIONS
 ARE DONE TO THE ORIGINAL DRAWINGS IN
 ORDER TO EXPEDITE THE REVIEW PROCESS.
 22-REVISE ENERGY CALCULATIONS:
 A)OWNER INFORMATION IS WRONG.
 B)MAKE SURE A/C AREA MATCHES FLOOR PLANS
 ONCE THEY ARE REVISED.
 23-PROVIDE PRODUCT APPROVAL FOR:
 A)HORIZONTAL ROLLING WINDOWS (DRAWINGS
 ARE NOT LEGIBLE).
 B)SINGLE HUNG WINDOWS.
 C)POCKET SLIDING GLASS DOORS AS SHOWN ON
 ARCHITECTURAL PLANS.
 D)SLIDING GLASS DOORS (DWGS NOT LEGIBLE)
 E)ENTRY DOORS (DRAWINGS NOT LEGIBLE)
 F)8070 GARAGE DOORS DRAWINGS (COMPLETE
 AND LEGIBLEDRAWINGS).
 G)FIXED WINDOWS. SEE SIZES ON PLANS.
 H)WINDOW MULLIONS.
 I)OVAL WINDOW.
 J)AWNING WINDOWS.
 K)ARCHED WINDOWS.
  
 24-STORM PANELS:
 A)PROVIDE COMPLETE INSTALLATION SCHEDULE
 AS PER CITY SAMPLE ATTACHED.
 B)PROVIDE KEY PLAN THAT MATCHES ACTUAL
 ARCHITECTURAL PLANS.
 C)STORM SHUTTERS PRODUCT APPROVAL IS
 GOOD ONLY FOR ONE PERMIT. SEE NOTE
 ON APPROVED STORM PANEL DRAWINGS.
 D)CLEARLY INDICATE ON DRAWINGS MOUNTING
 CONDITIONS AND ANCHOR TYPE & SPACING
 TO BE USED ACCORDING TO THE DESIGN
 PRESSURES, PANEL SPAN, EDGE DISTANCE
 AND STRUCTURE TO BE ATTACHED TO (WOOD
 OR CONCRETE BLOCK).