2002-01-26 00:00:00 | CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-BRING COPY OF PAID IMPACT FEES RECEIPT |
| 3-CLARIFY SHEARWALLS: |
| A)WHY THERE ARE TWO SHEARWALL SEGMENTS |
| SHOWN ON RIGHT ELEVATION ONLY. WHAT |
| ABOUT SHEARWALLS ON OTHER ELEVATIONS? |
| B)HOW ARE CORNERS AT 2ND FL. REINFORCED? |
| 4-SPECIFY NUMBER OF RIDGE VENTS ACCORD'G |
| TO CALCULATIONS DONE TO DETERMINE THE |
| VENTILATION REQUIRED BY SEC. 2309.7 |
| SBC 1997. THIS IS PART OF THE DESIGN |
| SPECIFICATIONS. |
| 5-SPECIFY THE DESIGN PRESSURES THAT WERE |
| CALCULATED AT EACH EXTERIOR OPENINGS |
| AS REQUIRED BY SEC. 1606 SBC 1997. |
| 6-AIR CONDITIONED SQUARE FOOTAGE IS |
| INCORRECT: |
| A)REVISE CALCULATIONS ON SHEET 2 OF 9. |
| B)GO TO PBC AND REVISE SQUARE FOOTAGE |
| FOR IMPACT FEES PURPOSE AS WELL. |
| C)CONSTRUCTION VALUE WILL BE ADJUSTED |
| WHEN PROVIDING CORRECT SQUARE FOOTAGE. |
| 7-SPECIFY/INDICATE ON PLANS WINDOWS TO |
| HAVE SAFETY GLASS. SEC. 2305.2 SBC/97. |
| 8-PROVIDE COMPLETE FRAMING DETAIL/SPECS |
| FOR SLIDING GLASS DOORS WITH POCKET BY |
| FAMILY AREA. SEC. 104.2.2 CITY AMENDM. |
| 9-PROVIDE ATTIC ACCESS AT FIRST FLOOR BY |
| BEDROOM #2 REAR ROOF. SEC. 2309.6 SBC |
| -PROVIDE ATTIC ACCESS AT 2ND FL. ROOF. |
| 10-PROVIDE EGRESS WINDOW FOR "GAME ROOM" |
| SEC. 1005.4 SBC 1997. FOR SAFETY |
| REASONS THIS ROOM IS CONSIDERED FOR |
| SLEEPING AS WELL. |
| 11-SPECIFY FASTENINGS FOR RAILINGS. SEC. |
| 1608.2 SBC 1997. |
| 12-REVISE RATIO OF STAIRS TO COMPLY WITH |
| SEC. 1007.3 SBC 1997. SEE COMMENTS ON |
| STAIR SECTIONS. SHEET 4 OF 9. |
| 13-PROVIDE COMPLETE WALL SECTIONS THRU |
| INTERIOR BEARING WALL BY FAMILY ROOM. |
| SEE COMMENTS ON SHEET 4 OF 9. |
| SECTION 104.2.2 CITY AMENDMENTS TO SBC |
| SAME APPLIES TO INT. WALL SECTION AT |
| FRONT AREA. |
| 14-LAUNDRY ROOM UNDER STAIRS TO COMPLY |
| WITH HEADROOM REQUIREMENTS OF SECTION |
| 1203.2 SBC 1997. |
| 15-ENG'R TO PROVIDE ORIGINAL SIGNATURE |
| ON SOIL TEST REPORT AS REQUIRED BY |
| CHAPTER 471 FLORIDA STATUTES. |
| 16-CLARIFY REINFORCEMENT FOR ENTRY COLS. |
| FOUNDATION PLANS AND SECTION DETAILS |
| DON'T MATCH. |
| 17-CLARIFY DETAIL 4 OF SHEET 8 OF 9. SEE |
| COMMENTS ON PLANS. |
| 18-ROOF FRAMING PLAN ON SHEET 9 OF 9 IS |
| VERY CONFUSING BECAUSE IT'S MIXING |
| 1ST AND SECOND FLOOR. ALSO, IT DOESN'T |
| MATCH EXTERIOR ELEVATIONS. REVISE. |
| 19-PROVIDE STRUCTURAL BUCK DETAIL FOR |
| EXTERIOR SWING DOORS. SEC. 104.2.2 |
| CITY AMENDMENTS AND SEC. 1606 SBC 1997 |
| 20-SPECIFY CEILING INSTALLATION AT ENTRY |
| AND REAR PORCHES. SEE ASTM C926 AND |
| ASTM C1063 FOR PROPER SPECIFICATIONS. |
| SECTION 2504.2 SBC 1997. |
| 21-SEE COMMENTS ON PLANS. INCLUDING |
| THOSE BY THE OTHER TRADES.PLEASE BRING |
| BACK REVIEWED SET AFTER CORRECTIONS |
| ARE DONE TO THE ORIGINAL DRAWINGS IN |
| ORDER TO EXPEDITE THE REVIEW PROCESS. |
| 22-REVISE ENERGY CALCULATIONS: |
| A)OWNER INFORMATION IS WRONG. |
| B)MAKE SURE A/C AREA MATCHES FLOOR PLANS |
| ONCE THEY ARE REVISED. |
| 23-PROVIDE PRODUCT APPROVAL FOR: |
| A)HORIZONTAL ROLLING WINDOWS (DRAWINGS |
| ARE NOT LEGIBLE). |
| B)SINGLE HUNG WINDOWS. |
| C)POCKET SLIDING GLASS DOORS AS SHOWN ON |
| ARCHITECTURAL PLANS. |
| D)SLIDING GLASS DOORS (DWGS NOT LEGIBLE) |
| E)ENTRY DOORS (DRAWINGS NOT LEGIBLE) |
| F)8070 GARAGE DOORS DRAWINGS (COMPLETE |
| AND LEGIBLEDRAWINGS). |
| G)FIXED WINDOWS. SEE SIZES ON PLANS. |
| H)WINDOW MULLIONS. |
| I)OVAL WINDOW. |
| J)AWNING WINDOWS. |
| K)ARCHED WINDOWS. |
| |
| 24-STORM PANELS: |
| A)PROVIDE COMPLETE INSTALLATION SCHEDULE |
| AS PER CITY SAMPLE ATTACHED. |
| B)PROVIDE KEY PLAN THAT MATCHES ACTUAL |
| ARCHITECTURAL PLANS. |
| C)STORM SHUTTERS PRODUCT APPROVAL IS |
| GOOD ONLY FOR ONE PERMIT. SEE NOTE |
| ON APPROVED STORM PANEL DRAWINGS. |
| D)CLEARLY INDICATE ON DRAWINGS MOUNTING |
| CONDITIONS AND ANCHOR TYPE & SPACING |
| TO BE USED ACCORDING TO THE DESIGN |
| PRESSURES, PANEL SPAN, EDGE DISTANCE |
| AND STRUCTURE TO BE ATTACHED TO (WOOD |
| OR CONCRETE BLOCK). |