Notes |
Date |
Text |
2002-01-12 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) MINIMUM FACILITIES FOR OFFICE SPACE | | OK, BUT WAREHOUSE USE IS UNCLEAR. WHAT | | TYPE OF WAREHOUSING IS GOING TO BE IN | | THIS SPACE. ACCORDING TO SHT A1, 43 | | PEOPLE WILL BE WORKING IN THE WAREHOUSE. | | FACILITIES SHALL BE REQUIRED FOR THOSE | | PEOPLE ALSO AT A RATE OF 2 MALE W/C'S & | | 2 LAVS AND 2 FEMALE W/C'S & 2 LAVS. 1 | | DRINKING FOUNTAIN IS REQUIRED FOR WARE- | | HOUSE ALSO. | | 2) SHTS A4 & A5 RESTROOMS 104 & 114. PER | | FACBC SEC 4.22.2 & 4.22.3 DOORS TO AN | | ADAPTABLE TOILET SHALL NOT SWING INTO | | THE CLEAR FLOOR SPACE OF ANY FIXTURE. | | 3) SHTS A4 & A5. MINIMUM FACILITIES SHOW | | 2 DRINKING FOUNTAINS REQUIRED. A HI-LOW | | IS CONSIDERED 1 FIXTURE. 1 MORE DRINKING | | FOUNTAIN IS REQUIRED. SPC TABLE 407 | | 4) SHTS A4 & A5, MENS RESTROOM HDCP | | STALL, W/C SHALL BE LOCATED IN THE COR- | | NER DIAGONAL FROM STALL DOOR. FACBC SEC | | 4.17.3(2). | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|