Plan Review Notes For Permit 01121242 |
Permit Number |
01121242 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-01-23 00:00:00 | ******************DENIED**************** | | | | | | 1.2 HR SEPERATION BETWEEN WAREHOUSE | | AND OFFICES, PLAN SHEET M2.1 SHOW | | THE 1 1/2 HOUR RATED DOORS BEING | | UNDERCUT.PLEASE CLARIFY. | | | | 2.IN REFERENCE TO BUILDING PLAN REVIEW | | COMMENTS #2, SHOULD THE "SHOWROOM" | | HAVE A 2 HR RATING, FIRE DAMPERS ARE | | REQUIRED FOR ANY DUCT PENETRATIONS. | | PLEASE REVISE PLANS ACCORDINGLY. | | | | 3.PLEASE CLARIFY THE USE OF THE "PHOTO | | MODEL SHOP" AND THE "PRODUCTION | | DEVELOPMENT" AREAS.INDICATE WHAT | | TYPE OF WORK IS TO BE DONE IN THESE | | ROOMS. | | | | 4.INDICATE ON THE PLANS THE USE OF | | THE WAREHOUSE.REFERENCE BUILDING | | PLAN REVIEW COMMENTS #1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|