Plan Review Notes
Plan Review Notes For Permit 01121242
Permit Number 01121242
Review Stop B
Sequence Number 1
Notes
Date Text
2002-01-05 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01121242
 1400 NORTHPOINT PARKWAY # 40
 CONT BUTTERS CONSTRUCTION
 TEL: (954)570-8111
  
 SBC= 1997 STANDARD BUILDING CODE
 FL ACC= 1997 FLORIDA ACCESSIBILITY CODE
  
 1)- WAREHOUSE- BSC 104.2.2. ADDITIONAL
 INFORMATION REQUIRED, THE TYPES OF MATER
 IALS TO BE STORED, QUANITIES, TYPE OF
 STORAGE UNITS, RACKS, THE HEIGTH OF THE
 RACKS, WILL FIRE SPRINKLERS BE INCORP-
 ARATED INTO THE RACK SYSTEMS? THIS ADDI-
 TIONAL INFORMATION SHALL BE NECESSARY
 BEFORE WE WILL BE ABLE TO CLASSIFY THE
 OCCUPANCY OF THE WAREHOUSE.
  
 2)- ROOM # 144 SHOWROOM, WITHOUT A LAY-
 OUT OF FURNATURE OR BETTER DISCRIPTION
 OF THE USE OF THIS ROOM, IT MAY APPEAR
 TO BE A, A-2 SMALL ASSEMBLY USAGE,
 1840 SQ FT @ 15 FT/PERSON= 122 OCCUPANTS
 IN THIS CASE (2) PROBLEMS OCCUR: (1)
 SBC TABLE 704.1 SHALL REQUIRE 2 HR SEPER
 ATION/ W 1 1/2 HR OPENING PROTECTION.
 704.1.2.2 THIS SPACE DOES NOT FALL UNDER
 EXEMPTIONS FOR ACCESSORY UES.(2) DOOR
 144B WOULD HAVE TO REVERSE THE SWING OF
 THE DOORS PER SBC 1004.1.2.(ROOMS WITH
 AN OCC LOAD > 50.
  
 3)- SHEET A-8 DETAIL "A" DEPICTS A 2 HR
 WALL ASSEMBLY, A UL LISTING OR U.S.
 GYPSUM NUMBER REQUIRED. SBC 705.1.2.
 WHAT TYPE OF FIRESTOP SYSTEM WILL BE
 USED AT THE METAL ROOF DECK ?
  
 4)- WAREHOUSE EGRESS:SBC 1001.1.3:
 IT IS CRITICAL THAT THE REQUIRED MEANS
 OF EGRESS BE DESIGNATED AND MAINTAINED
 TO INSURE THAT THESE OBSTRUCTIONS ARE
 ELIMINATED, SPECIAL MARKINGS OR SOME
 TYPE OF RAILING OR SCREENING MAY BE USED
 TO SEPERATE THEDESIGNATED MEANS OF
 EGRESS FROM THE STORAGE USE.
  
 5)- SHEET A-6/2 STAIR DETAIL, MORE
 INFORMATION SHALL BE REQUIRED. THERE IS
 NO INFORMATION ON THE SIDE WALLS OF THE
 ELEVATED LANDING. THE DETAIL ALSO INDICA
 TES AN EXISTING SLAB THAT CONTINUES
 UNDER THE BUILDING?!!
 GIVE THE CORRECT RISE & RUN SBC 1007.3.1
 NOT 7T@6 25/32. FOR THE GAURDRAIL INFOR-
 MATION LOOK AT THE 4" SPHERE DETAILED
 VS. SBC 1015.3, BOTTOM RAIL OF GUARDRAIL
 CLEARENCE FROM LANDING 2" NOT 4".
  
 6)- SHEET A-4 DETAIL A6/1 NEW EXTERIOR
 DOORWAY, SBC 1606.2.6.2 COMPONENTS AND
 CLADDING, PROVIDE 2 COPIES OF PRODUCT
 TESTING REPORT FOR LARGE MISSLE IMPACT
 RESISTANCE TESTING.EITHER SBCCI OR DADE
 COUNTY REPORTS ARE ACCEPTED.
  
 7)- PUBLIC RESTROOMS: SBC 1204.2
 SCHEDULE MISSING INFORMATION FOR CT-2?
  
 FLORIDA ACCESSIBILITY CODE:
 8)- DOOR 104-A 4.22.2/4.23.2 DOORS
 ACCESSIBILE TO BATHROOM SHALL COMPLY
 WITH 4.13 DOORS SHALL NOT SWING INTO THE
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
  
 9)- DOOR114-A SAME AS ABOVE.
  
 10)- MENS RESTROOM WATERCLOSET STALLS:
 4.17.3(2) SIZE & ARRANGEMENT ACCESSIBLE
 WATER CLOSET SHALL BE LOCATED IN THE
 CORNER DIAGONAL TO THE DOOR.
  
 SHEET# 5 DETAIL #1 UPPER CABINETS & THE
 MICROVAWE ARE OUT OF REACH, 4.2 SPACE
 & REACH RANGE, SEE ALSO A-5-10 &
 A-5 SEC 11.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412.