Plan Review Notes For Permit 01121239 |
Permit Number |
01121239 |
|
Review Stop |
R |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2002-10-18 00:00:00 | DENIED BY BUILDING | | | | 1) THE PRODUCT APPROVALS SUBMITTED ARE | | NOT LEGIBLE. | | | | 2) WINDOW REPLACEMENT WAS NOT INCLUDED | | IN THE SCOPE OF WORK FOR THE PERMIT THAT | | WAS ISSUED. A SEPARATE PERMIT WITH | | ADDITIONAL FEES BASED ON THE VALUE OF | | THE WORK IS REQUIRED. IF ANY WINDOWS ARE | | REPLACED IN A SLEEPING ROOM, THE WINDOWS | | MUST COMPLY THE WITH EMERGENCY EGRESS | | REQUIREMENTS OF FBC SEC.1005.4. | | PRODUCT APPROVALS AND A KEY PLAN SHOWING | | THE WINDOWS THAT ARE BEING REPLACED ARE | | REQUIRED. | | | | 3) IMPACT PROTECTION IS REQUIRED FOR ALL | | NEW WINDOWS. A SEPARATE PERMIT FOR STORM | | PANELS IS REQUIRED. PRODUCT APPROVALS, | | KEY PLANS AND INSTALLATION SCHEDULE IS | | REQUIRED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)659-8096 EXT.8202 |
|