2002-05-08 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 COMMENTS (3) & (4) BELOW HAVE NOW BEEN
 ADDRESSED BY THE ENGINEER.
  
 --PROVISO--
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
2002-05-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 2/27/02:
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SHEET 5, BUILDING SECTION.THE
 SIMPSON HGAM 10 TIES SPECIFIED TO ANCHOR
 THE NEW RAFTERS TO THE EXISTING TIE BEAM
 ARE STATED AS HAVING AN UPLIFT CAPACITY
 OF 827#.THIS IS THE ULTIMATE CAPACITY,
 THE ALLOWABLE LOAD IS 260# WHICH IS LESS
 THAN THE REQUIRED CAPACITY.SHEET 5,
 ROOF FRAMING PLAN,SPECIFIES SIMPSON H1
 (ALLOWABLE UPLIFT 490#) FOR THE SAME
 LOCATION, SO THE SHEET 5 REFERENCE TO
 SIMPSON HGAM 10 TIES SHOULD BE REMOVED.
  
 4) SHEET 2, FOUNDATION PLAN.THE COLUMN
 FOOTING SCHEDULE STATES THAT THE COLUMN
 C-1 POST IS SET IN A SIMPSON PB44 POST
 BASE.THIS DOES NOT HAVE SUFFICIENT
 UPLIFT CAPACITY AND DOES NOT CORRELATE
 WITH THE ANNOTATION FOR THE C-1 COLUMN
 FOOTINGS ADJACENT THE CORNER OF THE
 COVERED DECK.THIS STATES THAT SIMPSON
 ABU44 POST BASE ANCHORS ARE TO BE USED.
 AMEND THE COLUMN FOOTING SCHEDULE TO
 REFLECT THE ANNOTATION ON THE PLAN.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS