2001-12-18 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE NO MAIN DISCONNECT
 SHOWN AT DETACHED STRUCTURE.ART 225-31
  
 2)NOTE: PLEASE NOTE EASEMENT ISSUE STILL
 NEEDS TO BE RESOLVED.
  
 3)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 IS SHOWN COMING FROM PANEL THAT FEEDS
 COMMON STREET LIGHTING, PLEASE ALSO
 NOTE THAT SERVICE IS SUPPOSED TO BE
 COMING FROM A NEW SEPARATE METER FROM
 FPL, FROM ELEC ROOM IN "A" BLOCK/??
 PLEASE CLARIFY
  
 4)NOTE: PLEASE CLARIFY 4-2/0`S IS
 ONE OF THESE A GROUNDING CONDUCTOR?
 PLEASE CLARIFY TRANSFORMER GROUND?
 250-30
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 BILL STAPLES
 ASST BUILDING OFFICIAL
 659-8096 EXT 8315
 FOR ANY EASEMENT QUESTIONS.