2002-04-24 00:00:00 | DENIED |
| REFERENCE: SPC-94 - SGC-97 |
| |
| 1) SHT A-4 KITCHEN / LAUNDRY ROOM SANT. |
| RISER DIAGRAM DOES NOT REFLECT FLOOR |
| PLAN. SHOWS KITCHEN SINK BEING TAKEN OFF |
| BEFORE SALAD SINK. |
| 2) SHT A-4 SHOWS CLOUD AT RISER DIAGRAM |
| FOR SANT., 2ND FLOOR W/C - BIDET BUT |
| NOT ON FLOOR PLAN. PLEASE CLARIFY. |
| 3) SEPARATE PERMIT REQUIRED FOR GAS. |
| PLEASE PROVIDE GAS PERMIT APPLICATION |
| REQUIREMENT INFORMATION AS FOLLOWS. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER STANDARD |
| GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE STANDARD GAS CODE SECS. 305.2 THRU |
| 305.4 AND TABLES 305.4(A) THRU 305.4(E). |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| THE STANDARD GAS CODE SEC. 305.4(I). |
| F. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER THE STANDARD GAS |
| CODE SECS. 402.4 THRU 402.4.4.7. |
| G. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER STANDARD GAS CODE SEC. 305.2. IF |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| H. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER THE STANDARD GAS CODE SECS |
| 602 THRU 612. |
| I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| STANDARD GAS CODE SEC. 402. |
| J. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| K. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| |
| REVIEW BY KEN STEVENS |