Plan Review Notes
Plan Review Notes For Permit 01120918
Permit Number 01120918
Review Stop E
Sequence Number 2
Notes
Date Text
2002-03-08 00:00:00*************** UNSAT *****************
  
 PLEASE NOTE THAT NOTES 1,2,3 FROM FIRST
 REVIEW WERE NOT DONE.
  
 1)NOTE: PLEASE NOTE THAT NOTE#1 HAS
 2/0`S FOR 250AMP SERVICE? PLEASE NOTE
 THAT WHEN PLANS CAME BACK, THE CONDUCTOR
 SIZE WENT EVEN SMALLER, DOWN TO 1/0`S?
 PLEASE NOTE THAT CONDUCTORS ARE TO BE
 SIZED PER NEC 310-15/16.
 310-15, 250A SERVICE IS A MIN OF 4/0`S.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT THIS IS REQ`D AT TIME
 OF REVIEW OF PLANS. 110-9/215-5.
  
 3)NOTE: PLEASE NOTE THAT RISER STILL
 DOES NOT SHOWN AN EQUIPMENT GROUNDING
 CONDUCTOR BETWEEN MAIN DISCONNECT AND
 PANEL. 250-122.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. ONCE AGAIN, PLEASE CALL IF THERE
 ARE ANY QUESTIONS,OR GOING OVER THE PLAN
 -S WOULD BE BETTER SUITED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372