2002-03-15 00:00:00 | BUILDING PLAN REVIEW |
| 01120918 |
| 727 SUNSET |
| |
| ********PROVISO********* |
| 1) SHEET A-7 TWO- STORY WALL SECTION, |
| INDICATES THAT 2X4 WOOD TRUSSES MAKE UP |
| THE SECOND STORY CEILING / ROOF FRAMING |
| ASSEMBLY. ENGINEER TO CERTIFY THAT THE |
| TRUSSES WILL ACCEPT THE ADDTIONAL LOAD- |
| ING. IF DIAGONAL WEBBING REMOVED ENGIN- |
| EER IS TO DESIGN THE TRANSFER OF LOADING |
| |
| 2) THE NEW STAIRWAY LEADING TO THE 3RD |
| FLOOR INDICATES A TRUE 3RD FLOOR.TABLE |
| 500 REQUIRES A 1 HR RATING, THIS IS ACCO |
| MPLISHED THROUGH TABLE 709.6.2A & B |
| TIME ASSIGNED TO WOOD FRAMING, INSULA- |
| TION & WALLBOARD MEMBRANE. |
| |
| 3) THE 3RD STORY IF CONVERTED FROM |
| STORAGE TO A HABITAL OCCUPANCY SHALL |
| NEED TO MEET THE FOLLOWING CODE SECTIONS |
| 1997 STANDARD BUILDING CODE |
| 1203.1 7'-6" CEILING HEIGTH. |
| 1203.2.2. SLOPED CEILING, 1/2 AREA THERE |
| OF. |
| 1004.1.2 EVERY ROOM OR TENANT SPACE |
| SHALL BE PROVIDED WITH A MINIMUM OF ONE |
| MEANS OF EGRESS.1004.1 FOR EVERY SLEEP- |
| ING ROOM ON THE 1ST, 2ND OR 3RD STORY |
| AAT LEAST ONE EXTERIOR EMERGENCY ESCAPE |
| AND RESCUE OPENING IS REQUIRED. FOR THE |
| 3RD FLOOR A MINIMUM OF 5.7 SQ. FT OF |
| CLEAR OPEN AREA PER SLEEPING ROOM. |