Plan Review Notes
Plan Review Notes For Permit 01120918
Permit Number 01120918
Review Stop B
Sequence Number 2
Notes
Date Text
2002-03-15 00:00:00BUILDING PLAN REVIEW
 01120918
 727 SUNSET
  
 ********PROVISO*********
 1) SHEET A-7 TWO- STORY WALL SECTION,
 INDICATES THAT 2X4 WOOD TRUSSES MAKE UP
 THE SECOND STORY CEILING / ROOF FRAMING
 ASSEMBLY. ENGINEER TO CERTIFY THAT THE
 TRUSSES WILL ACCEPT THE ADDTIONAL LOAD-
 ING. IF DIAGONAL WEBBING REMOVED ENGIN-
 EER IS TO DESIGN THE TRANSFER OF LOADING
  
 2) THE NEW STAIRWAY LEADING TO THE 3RD
 FLOOR INDICATES A TRUE 3RD FLOOR.TABLE
 500 REQUIRES A 1 HR RATING, THIS IS ACCO
 MPLISHED THROUGH TABLE 709.6.2A & B
 TIME ASSIGNED TO WOOD FRAMING, INSULA-
 TION & WALLBOARD MEMBRANE.
  
 3) THE 3RD STORY IF CONVERTED FROM
 STORAGE TO A HABITAL OCCUPANCY SHALL
 NEED TO MEET THE FOLLOWING CODE SECTIONS
 1997 STANDARD BUILDING CODE
 1203.1 7'-6" CEILING HEIGTH.
 1203.2.2. SLOPED CEILING, 1/2 AREA THERE
 OF.
 1004.1.2 EVERY ROOM OR TENANT SPACE
 SHALL BE PROVIDED WITH A MINIMUM OF ONE
 MEANS OF EGRESS.1004.1 FOR EVERY SLEEP-
 ING ROOM ON THE 1ST, 2ND OR 3RD STORY
 AAT LEAST ONE EXTERIOR EMERGENCY ESCAPE
 AND RESCUE OPENING IS REQUIRED. FOR THE
 3RD FLOOR A MINIMUM OF 5.7 SQ. FT OF
 CLEAR OPEN AREA PER SLEEPING ROOM.