2002-01-07 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01120918
 727 SUNSET RD.
 CONT.: ROGER G. THOMAS
 TEL: (561)575-1389
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- NOTICE OF COMMENCEMENT MUST BE RE-
 CORDED AT THE COUNTY COURTHOUSE BEFORE
 THE PERMIT MAY BE ISSUED.
  
 2)- SBC 1804.2.7.2 SOILS TEST TO VERIFY
 THE MINIMUM SAFE BEARING VALUE.
  
 3)- ADDITIONAL INFORMATION REQUIRED:
 AVERAGE EAVE HEIGTH=
 BASIC PRESSURE=
 SHEET A-2 MISSING THIS INFORMATION. THE
 PRESSURE ZONES FOR ALL EXTERIOR OPENINGS
 (WINDOWS & DOORS) SHOW ON ELEVATIONS.
  
 4)-MISSING ENERGY CALCS,
  
 5)- SHEET A-4 DEPICTS A THIRD STORY,
 ATTIC LOFT AND FUTURE BATH, THIS WOULD
 REQUIRE THIS STRUCTURE TO BE A TYPE VI
 1-HOUR PROTECTED BUILDING.
 A) TABLE 600 TYPE V1 PROTECTED INDICATE
 THE 1 HR PROTECTION FOR ALL STRUCTUR
 AL MEMBERS AS REQUIRED BY TABLE 600.
 B) GIVE A CUT SECTION THROUGH THE 3
 FLOORS INDICATING THE HEIGTH OF EACH
 STORY, SBC 1203.2.1 OCCUPLIABLE ROOMS
 AND HABITABLE SPACES SHALL NOT HAVE A
 CEIL LESS THAN 7'-6", STORAGE, BATHROOMS
 MAY BE 7'-0". IF ANY ROOM IN A BUILDING
 HAS A SLOPING CEILING, THE PRESCRIBED
 CEILING HEIGTH FOR THE ROOM IS REQUIRED
 IN ONLY 1/2 THE AREA THEREOF.(1203.2.2)
 6) SHEET A-6
 DISCREPANCY BETWEEN FLOOR PLAN NEW
 WINDOWS AND SHEETS 5/SHEET6. IN REVIEW-
 ING PLANS WITH HISTORICS THEY INDICATE
 THAT NEITHER DRAWING IS CORRECT BUT
 CASEMENT WINDOWS SHALL BE INSTALLED?
  
 7) SHEET A-5 INDICATES WINDOWS WITH MULL
 ION, WINDOW REPORT INDICATES THAT THIS
 REPORT IS FOR SINGLE UNIT APPLICATION.
 REPORT REQUIRED FOR MULLION.
  
 8) FRENCH DOOR REPORT SHALL REQUIRE
 LARGE MISSLE IMPACT RESISTANCE PROTEC-
 TION.
  
 9) SHEET A-11 THE FIRST FLOOR FRAMING
 PLAN INDICATES A DOUBLE 2X12 BEAM AROUND
 THE PERIMETER OF THE PORCH, WHAT TYPE
 OF SUPPORT IS USED WHERE WOOD BEAM ENDS
 AT WALL LINE? SECTION OF KITCHEN WHERE
 WALL WAS REMOVED, WHAT TYPE OF CONNEC-
 TION IS TO BE USED FOR 6X6 POST AND FOR
 GIRDER, DOES THE EXISTING 2ND FLOOR
 JOIST BEAR ON THIS WALL?
  
 10)- SHEET A-7 SECTION 2 STORY INDICATES
 STUCCO ALL THE WAY TO THE GROUND, A 6"
 AIR GAP REQUIRED TERMITE PROTECTION,
 SBC2304.2.5 AMENDMENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412