Plan Review Notes
Plan Review Notes For Permit 01120902
Permit Number 01120902
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-05 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS A MAIN BUT MAIN IS NOT SHOWN ON
 PLANS? PLEASE SHOW.
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING BETWEEN MAIN AND PANEL.
 250-122
  
 3)NOTE: PLEASE NOTE 384-7 AND 110-26,
 PLEASE SHOW LAYOUT FOR REQ`D CLEARENCES
 FOR PANEL IN STORAGE ROOM OR LABEL
 ROOM FOR ELECTRICAL/MECH EQUIPMENT ROOM
 ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372