Plan Review Notes For Permit 01120902 |
Permit Number |
01120902 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-13 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | SBC = STANDARD BUILDING CODE 1997 | | SBC*= STANDARD BUILD'G CODE (CITY AMEND) | | | | 1) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) SBC 1804.1.3SHEET S-1, SECTION 1. | | THE BASE OF THE EXTERIOR WALL FOUNDATION | | SHALL BE AT LEAST 12" BELOW FINISH GRADE | | | | 3) SBC* 1804.2A SOIL REPORT SHALL BE | | SUBMITTED TO CONFIRM THE DESIGN | | ASSUMPTIONS. | | | | 4) SBC 2309.2 AND SBC* 104.2SUBMIT | | SIGNED AND SEALED TRUSS SHOP DRAWINGS | | ANDDESIGN CALCULATIONS. | | | | 5) SHEET S-1, SECTION 5 AND 'NOTE 2'. | | THE STATED 'USP' RTPGA820 AND RTPGA824 | | ARE NOT VALID USP CONNECTOR REFERENCES. | | AMEND THE NOTES TO CLARIFY THE PROPOSALS | | | | 6) SBC* 1707.4 AND SBC* 104.1.1 EXTERIOR | | DOOR ASSEMBLIES.THE SUBMITTED PRODUCT | | APPROVAL STATES THAT HURRICANE SHUTTERS | | ARE REQUIRED.A SEPARATE SHUTTER PERMIT | | APPLICATIO IS REQUIRED. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|