Plan Review Notes
Plan Review Notes For Permit 01120706
Permit Number 01120706
Review Stop E
Sequence Number 1
Notes
Date Text
2001-12-26 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO BE SHOWM PER 220-11/-13 ETC.
  
 2)NOTE: PLEASE NOTE, ALL CONTINOUS LOADS
 NEED TO BE SHOWN AT 125%.215-2-3 AND
 230-42.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372