Plan Review Notes For Permit 01120616 |
Permit Number |
01120616 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-12-11 00:00:00 | 1) FIRE ALARM NOTES INDICATES CLASS B, | | STYLE C CIRCUITS. ONLY CLASS A, STYLE | | D CIRCUITS WILL BE ALLOWED. | | 2) EXITING IS NOTED THRU THE HUMAN | | RESOURCE RECEPTION AND THE BOARDROOM. | | THESE DOORS CAN NEVER BE LOCKED AS THEY | | COULD PREVENT EXIT ACCESS TO THE EXITS. | | 3) NO FIRE SPRINKLER DRAWINGS PROVIDED | | WITH PLANS. | | 4) PLEASE INDICATE OCCUPANT LOAD FOR | | OPERATIONS AREA 115. IT WAS NOTED THAT | | ONE OF THE EXIT DOORS OPEN INWARDS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|