Plan Review Notes
Plan Review Notes For Permit 01120616
Permit Number 01120616
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-12-11 00:00:001) FIRE ALARM NOTES INDICATES CLASS B,
 STYLE C CIRCUITS. ONLY CLASS A, STYLE
 D CIRCUITS WILL BE ALLOWED.
 2) EXITING IS NOTED THRU THE HUMAN
 RESOURCE RECEPTION AND THE BOARDROOM.
 THESE DOORS CAN NEVER BE LOCKED AS THEY
 COULD PREVENT EXIT ACCESS TO THE EXITS.
 3) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 4) PLEASE INDICATE OCCUPANT LOAD FOR
 OPERATIONS AREA 115. IT WAS NOTED THAT
 ONE OF THE EXIT DOORS OPEN INWARDS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910