Plan Review Notes
Plan Review Notes For Permit 01120298
Permit Number 01120298
Review Stop P
Sequence Number 2
Notes
Date Text
2002-02-02 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A-1 SHOW CLEAR FLOOR SPACE AND
 TURNING RADIUS FOR TOILET ROOM.
 2) SHT A-1 MINIMUM FIXTURES REQUIREMENTS
 SPC TABLE 407 REQUIRE A DRINKING FOUNT-
 AIN.
 3) SHT A-1 SANT RISER DIAGRAM, MOP SINK
 NOT SHOWN.
 4) SHT A-1 WATER RISER DIAGRAM, PLEASE
 LOCATE WATER HAMMER ARRESTORS NEAR FIX-
 TURES IN "EFFECTIVE RANGE" NOT AT TOP OF
 DROP AS SHOWN PER PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 5) BACKFLOW REQUIRED ON WATER SERVICE.
  