Plan Review Notes
Plan Review Notes For Permit 01120298
Permit Number 01120298
Review Stop M
Sequence Number 2
Notes
Date Text
2002-01-31 00:00:00*******************DENIED***************
  
  
 COMMENT #2 FROM REVIEW DATED 12-18-0 WAS
 NOT ADDRESSED.
  
 PROVIDE DETAIL OF EXHAUST TERMINATION.
 AS PER NFPA 33 AIR EXHAUSTED SHALL BE
 CONDUCTED BY DUCTS DIRECTLY TO THE
 OUTSIDE OF THE BUILDING BY THE MOST
 DIRECT ROUTE TO THE POINT OF DISCHARGE.
 (SHALL NOT PENETRATE FIRE WALL)THE
 EXHAUST DUCT DISCHARGE SHALL BE AT
 LEAST 6 FT FROM ANY EXTERIOR WALL OR
 ROOF.DUCT SHALL NOT DISCHARGE IN THE
 DIRECTION OF ANY COMBUSTIBLE
 CONSTRUCTION THAT IS WITHIN 25 FT OF
 THE EXHAUST DISCHARGE POINT NOR SHALL
 IT DISCHARGE IN THE DIRECTIONS OF ANY
 UNPROTECTED IN NONCOMBUSTIBLE OR
 LIMITED COMBUSTIBLE CONSTRUCTIONS THAT
 IS WITHIN 25 FT OF THE EXHAUST
 DISCHARGE POINT.
  
 INDICATE ON PLAN HOW EXHAUST DUCT
 TERMINATION WILL BE SECURED TO THE ROOF.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.