Plan Review Notes
Plan Review Notes For Permit 01120298
Permit Number 01120298
Review Stop P
Sequence Number 1
Notes
Date Text
2002-01-03 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLEASE SUBMIT CALCULATIONS FOR MIN-
 IMUM FACILITIES PER SPC TABLE 407. GIVE
 INFORMATION ON NUMBER OF PERSONS WORKING
 PER SHIFT ECT. SQUARE FOOTAGE OF SPACE
 REQUIRED.
  
 2) SHT A1, WATER RISER DIAGRAM, AIR
 CHAMBERS SHALL HAVE ACCESS PANELS AND
 SHALL BE RECHARGEABLE PER SPC SEC
 607.8.3. APPROVED WATER HAMMER ARRESTORS
 DO NOT REQUIRE ACCESS AND ARE NOT RECHAR
 GEABLE.
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT 8377