Plan Review Notes For Permit 01120298 |
Permit Number |
01120298 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-01-03 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) PLEASE SUBMIT CALCULATIONS FOR MIN- | | IMUM FACILITIES PER SPC TABLE 407. GIVE | | INFORMATION ON NUMBER OF PERSONS WORKING | | PER SHIFT ECT. SQUARE FOOTAGE OF SPACE | | REQUIRED. | | | | 2) SHT A1, WATER RISER DIAGRAM, AIR | | CHAMBERS SHALL HAVE ACCESS PANELS AND | | SHALL BE RECHARGEABLE PER SPC SEC | | 607.8.3. APPROVED WATER HAMMER ARRESTORS | | DO NOT REQUIRE ACCESS AND ARE NOT RECHAR | | GEABLE. | | | | REVIEW BY KEN STEVENS | | (561) 569-8096 EXT 8377 |
|