2001-12-11 00:00:00 | 1) WHAT WILL THE SPRAY BOOTH BE USED |
| FOR. |
| 2) THE SPRAY BOOTH REQUIRES A FIRE |
| SUPPRESSION SYSTEM. SEPARATE PLANS AND |
| PERMITS REQUIRED FOR SPRAY BOOTH. |
| 3) THE SPRAY BOOTH REQUIRES THREE FEET |
| AROUND IT FOR CLEANING PURPOSES. |
| 4) THE SPRAY BOOTH REQUIRES GROUNDING. |
| 5) IF THE SPRAY BOOTH IS USED TO SPRAY |
| FLAMMABLE OR COMBUSTIBLE LIQUIDS, WHERE |
| WILL THESE ITEMS BE STORED WHEN NOT |
| BEING SPRAYED. |
| 6) PLEASE DEMONSTRATE COMPLIANCE WITH |
| THE STANDARD MECHANICAL CODE, SECTION |
| 506.1 WHICH REQUIRES THE EXHAUST DUCT |
| TO BE AT LEAST 10 FEET FROM THE |
| BUILDING, ADJACENT BUILDINGS, |
| PROPERTIES, PARKING AREAS, ETC. |
| 7) NO ELEVATION DRWAINGS OF THE |
| BUILDING PROVIDED. |
| 8) PLEASE INDICATE HOW MAKE-UP AIR IS |
| BEING PROVIDED FOR THE SPRAY BOOTH. |
| 9) PLEASE INDICATE LOCATIONS OF FIRE |
| EXTINGUISHERS. |
| 10) PLEASE INDICATE LOCATIONS OF |
| WRNING SIGNS ASSOCIATED WITH SPRAY |
| BOOTH. |
| 11) ELECTRICAL REQUIREMENTS TO COMPLY |
| WITH NFPA 33 REQUIREMENTS. |
| 12) IS THE WALL ADJACENT TO THE SPRAY |
| BOOTH A DEMISING WALL OR AN EXTERIOR |
| WALL. |
| |