2001-12-11 00:00:001) WHAT WILL THE SPRAY BOOTH BE USED
 FOR.
 2) THE SPRAY BOOTH REQUIRES A FIRE
 SUPPRESSION SYSTEM. SEPARATE PLANS AND
 PERMITS REQUIRED FOR SPRAY BOOTH.
 3) THE SPRAY BOOTH REQUIRES THREE FEET
 AROUND IT FOR CLEANING PURPOSES.
 4) THE SPRAY BOOTH REQUIRES GROUNDING.
 5) IF THE SPRAY BOOTH IS USED TO SPRAY
 FLAMMABLE OR COMBUSTIBLE LIQUIDS, WHERE
 WILL THESE ITEMS BE STORED WHEN NOT
 BEING SPRAYED.
 6) PLEASE DEMONSTRATE COMPLIANCE WITH
 THE STANDARD MECHANICAL CODE, SECTION
 506.1 WHICH REQUIRES THE EXHAUST DUCT
 TO BE AT LEAST 10 FEET FROM THE
 BUILDING, ADJACENT BUILDINGS,
 PROPERTIES, PARKING AREAS, ETC.
 7) NO ELEVATION DRWAINGS OF THE
 BUILDING PROVIDED.
 8) PLEASE INDICATE HOW MAKE-UP AIR IS
 BEING PROVIDED FOR THE SPRAY BOOTH.
 9) PLEASE INDICATE LOCATIONS OF FIRE
 EXTINGUISHERS.
 10) PLEASE INDICATE LOCATIONS OF
 WRNING SIGNS ASSOCIATED WITH SPRAY
 BOOTH.
 11) ELECTRICAL REQUIREMENTS TO COMPLY
 WITH NFPA 33 REQUIREMENTS.
 12) IS THE WALL ADJACENT TO THE SPRAY
 BOOTH A DEMISING WALL OR AN EXTERIOR
 WALL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910