Plan Review Notes For Permit 01120245 |
Permit Number |
01120245 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-12-21 00:00:00 | DENIED | | REFERENCE: SPC-94-FHA-AMEND-98 | | DESIGN MANUAL | | | | 1) SHT A1_MP-1 WATER RISER DIAGRAM, AIR | | CHAMBERS TO HAVE ACCESS PANELS AND SHALL | | BE RECHARGEABLE WITH VALVES AS REQUIRED | | IN SPC SEC 607.8.3. EITHER REMOVE OR | | SHOW DETAILS ON PLANS. (SEE ATTACHED | | SHEET) | | | | 2) SHT A_MP-3 PLUMBING NOTES AND SPECS. | | #4. AIR CHAMBERS REQUIRE ACCESS AND MUST | | BE RECHARGEABLE. SEE COMMENT #1. ALSO | | APPROVED WATER HAMMER ARRESTORS DO NOT | | REQUIRE ACCESS AND ARE RECOMMENDED. | | | | 3) THIS CONDITION IS TYPICAL OFF ALL | | WATER RISER DIAGRAMS FOR ALL UNITS. | | PLEASE CORRECT AND SHOW DETAILS ON PLANS | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|