Plan Review Notes
Plan Review Notes For Permit 01120245
Permit Number 01120245
Review Stop P
Sequence Number 1
Notes
Date Text
2001-12-21 00:00:00DENIED
 REFERENCE: SPC-94-FHA-AMEND-98
 DESIGN MANUAL
  
 1) SHT A1_MP-1 WATER RISER DIAGRAM, AIR
 CHAMBERS TO HAVE ACCESS PANELS AND SHALL
 BE RECHARGEABLE WITH VALVES AS REQUIRED
 IN SPC SEC 607.8.3. EITHER REMOVE OR
 SHOW DETAILS ON PLANS. (SEE ATTACHED
 SHEET)
  
 2) SHT A_MP-3 PLUMBING NOTES AND SPECS.
 #4. AIR CHAMBERS REQUIRE ACCESS AND MUST
 BE RECHARGEABLE. SEE COMMENT #1. ALSO
 APPROVED WATER HAMMER ARRESTORS DO NOT
 REQUIRE ACCESS AND ARE RECOMMENDED.
  
 3) THIS CONDITION IS TYPICAL OFF ALL
 WATER RISER DIAGRAMS FOR ALL UNITS.
 PLEASE CORRECT AND SHOW DETAILS ON PLANS
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377