Plan Review Notes For Permit 01120210 |
Permit Number |
01120210 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-12-21 00:00:00 | DENIED | | REFERENCE: SPC-94 - FHA-AMEND-98 DESIGN | | MANUAL | | | | 1) SHTS BR_MP-1, A1_MP-1, B_MP-1 & A3_ | | MP-1. WATER RISER DIAGRAMS, AIR CHAMBERS | | TO HAVE ACCESS PANELS AND SHALL BE RE- | | CHARGEABLE WITH VALVES AS REQUIRED IN | | SPC SEC 607.8.3 AND PDI-WH 201. EITHER | | REMOVE OR SHOW DETAILS ON PLANS FOR | | ACCESS AND HOW THEY WILL BE RECHARGED. | | (SEE ATTACHED SHEET) | | | | 2) SHT BR_MP-4, A_MP-3, & B_MP-4, PLUMB- | | ING NOTES AND SPECS #4. AIR CHAMBERS RE- | | QUIRE ACCESS AND MUST BE RECHARGEABLE. | | (SEE COMMENT #1) ALSO APPROVED WATER | | HAMMER ARRESTORS DO NOT REQUIRE ACCESS | | AND ARE RECOMMENDED. | | | | 3) THIS CONDITION IS TYPICAL OF ALL | | WATER RISER DIAGRAMS IN ALL UNITS. | | PLEASE CORRECT ON PLANS AND SHOW DETAILS | | | | REVIEW BY KEN STEVENS | | (561) 569-8096 EXT 8377 |
|