2001-12-10 00:00:00 | *******************PROVISO************** | | | | (ON PLAN) | | | | AIR FROM RESTROOMS SHALL NOT BE | | RECIRCULATED. 1997 SMC 503.3.1. | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS FOR | | SYSTEMS WITH FAN CAPACITY GREATER THAN | | 2,000 CFM.NOTIFICATION TO ALARM/STROBE | | IN NORMALLY OCCUPIED AREAS. | | 1997 SMC 406.1 & NFPA 90A 4-.4.4.3. |
|