Plan Review Notes For Permit 01120180 |
Permit Number |
01120180 |
|
Review Stop |
ENG |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-12-11 00:00:00 | FAILED : | | 1. PLEASE PROVIDE WATER SERVICE FOR RPZ | | AT LIFT STATION. | | 2. PLEASE PROVIDE EASMENT FOR THE | | PROPOSED LIFT STATIONS. | | 3. JACK & BORE, SHEET 2 OF 13 | | A) PLAN SHOWS 8" PVC @ 0.42% | | B) DETAILS SHOWS 18" CASING @ 0.75% | | C) SHEET 4 OF 13(SANITARY SEWER PROFILE) | | SHOWS 8" DIP @ 0.75% (FROM MH4 TO MH5) | | D) PLEASE CLARIFY | | 4. PLEASE REFER TO CITY STANDARD P-12 ON | | SHEET 10 OF 13 FOR CARRIER PIPE SIZE & | | CASING SIZE AND THICKNESS REQUIREMENT. | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | EXT. 8492 MOHAMMAD R. AMINI. |
|