Plan Review Notes For Permit 01120137 |
Permit Number |
01120137 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-02-09 00:00:00 | APPROVED WITH PROVISO: | | 1-FLOOD ZONE AO. NEED TO PROVIDE THE | | ELEVATION CERTIFICATE. | | 2-COMPLETE TWO HOUR WALL SECTION SHOWING | | ONE HOUR FIRE RATED ASSEMBLY AT INTER- | | SECTION OF 1ST FL. CONCRETE BLOCK WALL | | AND 2ND FLOOR FRAMING WALL. TABLE 600 | | SBC 1997 REQUIRES ONE HOUR FIRE RATED | | WALL CONTINUOUS FROM FOOTING TO TOP PL | | 3-SPECIFY ON PLANS ONE HOUR FIRE RATED | | GLASS BLOCK AT ZERO LOT LINE AS REQ'D | | BY TABLE 600 SBC 1997. SPECIFY CORRECT | | UL LISTING AND SPECS. | | 4-SPECIFY DRAFSTOPPING MATERIAL AND | | LOCATION ON SECOND FLOOR FRAMING PLAN. | | SEC. 2305.2.2 SBC 1997. | | 5-PROVIDE PRODUCT APPROVAL FOR: | | A)FIXED WINDOWS. SEE EXT. ELEVATIONS. | | B)ENTRY DOORS WITH LEGIBLE DRAWINGS. | | | | 6-SPECIFY TRUSS ANCHOR THAT WILL RESIST | | THE UPLIFT LOADS CALCULATED ON THE | | ENGINEERED TRUSSES. SEE ENGINEERING | | FOR TRUSS WD7. |
|