2002-01-16 00:00:00 | CHECKLIST: |
| 1-NEED TO RECORD NOTICE OF COMMENCEMENT. |
| 2-PROVIDE EGRESS FROM LOFT AREA AS REQ'D |
| BY SECTION 1005.4 SBC 1997. |
| 3-PROVIDE ATTIC ACCESS AT FRONT AREA OF |
| FIRST FLOOR ROOF. SEC. 2309.6 SBC 1997 |
| AND SPECIFY SIZE OF ATTIC ACCESS |
| LEADING TO FAMILY AREA ROOF. |
| 4-SPECIFY ONE HOUR FIRE RATED WALL FOR |
| ZERO LOT LINE WOOD FRAMED WALL. AS |
| REQUIRED BY TABLE 600 SBC 1997. |
| NOTE: 1 HR FIRE RATED BASED ON EXTERIOR |
| AND INTERIOR FIRE EXPOSURE. SEE NOTE |
| I ON TABLE 600 SBC 1997. |
| 5-PROVIDE 29" MINIMUM CLEAR OPENING AT |
| MASTER BATHROOM. SEE ENTRANCE TO WATER |
| CLOSET RM. CHAPTER 11 OF FLORIDA |
| ACCESSIBILITY CODE, 1997 ED. |
| 6-SPECIFY DRAFSTOPPING MATERIAL AND |
| LOCATION ON 2ND FLOOR FRAMING PLAN. |
| SEC. 2305.2.2 SBC 1997. |
| 7-PROVIDE COMPLETE SECTION/DETAIL FROM |
| FOOTING TO ROOF AT INTERIOR FRAMED |
| BEARING WALL. SPECIFY ALL FASTENERS. |
| SEC. 104.2.2 CITY AMENDMENTS TO SBC/97 |
| 8-2 STORY BEARING WALL ON SHEET 5.2 |
| DOESN'T MATCH FRAMING PLANS. REVISE. |
| 9-PROVIDE DETAILS AND COMPLETE SPECS FOR |
| CEILING INSTALLATION AT ENTRY AND REAR |
| PORCHES. SEE ASTM C926 AND ASTM C1063. |
| 10-REVISE TREAD/RISER RATIO ON STAIRS |
| SECTION. SEC. 1007.3 SBC 1997. |
| 11-PROVIDE SMOKE DETECTOR AT FIRST FLOOR |
| ALSO AS REQ'D BY SEC. 905.2.2 SBC 1997 |
| 12-PROVIDE PRODUCT APPROVAL FOR: |
| A)SINGLE HUNG WINDOWS (EXPIRED). |
| B)ARCHED WINDOW (EXPIRED). |
| C)1 HR GLASS BLOCK ASSEMBLY INFORMATION |
| IS TOO OLD. PROVIDE CURRENT 1 HR FIRE |
| RATED UL ASSEMBLY AND/OR ONE HOUR FIRE |
| RATED GLASS BLOCK PRODUCT APPROVAL. |
| D)ENTRY DOORS (EXPIRED). |
| |
| 13-CONNECTORS SPECIFIED FOR TRUSS WD7 |
| DON'T RESIST THE UPLIFT LOADS THAT |
| WERE CALCULATED ON ENGINEERED TRUSSES. |
| REVISE AS REQUIRED. |
| -SPECIFY CONNECTORS FOR TRUSSES FGE4 & |
| FGE7. SEE ENGINEERED TRUSSES. |
| 14-UPDATE/REVISE ALL GENERAL TRUSS DWGS |
| AS REQUIRED. SEE COMMENTS. |
| 15-ENGINEER OF RECORD WHO REVIEW ALL THE |
| TRUSS DWGS TO CLEARLY INDICATE THE |
| NAME OF FIRM WHO REVIEWED THE DWGS. |
| USE STANDARD REVIEW STAMP, IF POSSIBLE |
| 16-SEE PLANS FOR ADDITIONAL COMMENTS AND |
| BRING BACK REVIEWED SET IN ORDER TO |
| EXPEDITE THE REVIEW PROCESS. |