Plan Review Notes
Plan Review Notes For Permit 01120053
Permit Number 01120053
Review Stop E
Sequence Number 2
Notes
Date Text
2002-01-02 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT NOW HEAT PUMP
 SPEC AND LOAD CALCUALTIONS WERE SUBMITT-
 -ED BUT WIRING DIAGRAM STILL DOESN'T
 REFLECT ANY ASSC WIRING.
 PLEASE NOTE HEAT PUMP AND WIRING/CONDUIT
 AND WIRE SIZES MUST BE SHOWN ON PLANS.
 PLEASE ALOS NOTE THAT ALL CHANGES MUST
 BE DONE BY THE ENGINEER OF RECORD.
 FS/FAC 471.025.
  
 2)NOTE: PLEASE CLARIFY SERVICE, LOAD
 CALCS SHOW TWO 100A PANELS? PLEASE
 CLARIFY HOW THESE TWO PANELS ARE GETTING
 THEIR FEEDS? ARE THEY COMING FROM A 200A
 METERCAN AND SERVICE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANYQUESTIONS,
 PLEASE CALL.
  
 DEWEYPALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372