2001-12-06 00:00:001) WHAT PREVENTS THE HOSE FROM KINKING
 AFTER IT IS CONNECTED TO THE FIRE
 DEPARTMENT CONNECTION SINCE THE RISERS
 WILL BE LOCATED ON THE SIDES OF THE
 BUILDING.
 2) IT WAS NOTED ON THE SPEC BOOKS AND
 ON THE PLANS THAT CENTRAL BRAND FIRE
 SPRINKLER HEADS WILL BE USED. LF
 SPRINKLER HEADS WERE NOTED ON THE
 VOLUNTARY RECALL LIST FROM CENTRAL,
 PLEASE SEE WWW.SPRINKLERREPLACEMENT.COM.
 3) PLEASE EXPLAIN WHY THE SPARE
 SPRINKLER HEADS WILL BE STORED IN
 THE CLUBHOUSE AS OPPOSED TO THE
 INDIVIDUAL BUILDINGS.
 4) A 2 1/2 FDC WILL BE REQUIRED.
 5) WHAT PREVENTS THE VALVE FROM BEING
 CLOSED ON THE UNDERGROUND FIRE LINE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910