2001-12-06 00:00:001) WHAT PREVENTS THE HOSE FROM KINKING
 AFTER IT IS CONNECTED TO THE FIRE
 DEPARTMENT CONNECTION SINCE THE RISERS
 WILL BE LOCATED ON THE SIDES OF THE
 BUILDING.
 2) IT WAS NOTED IN THE SPEC BOOKS AND
 THE PLANS THAT CENTRAL BRAND FIRE
 SPRINKLER HEADS TYPE LF WILL BE
 USED. LF SPRINKLER HEADS WERE NOTED
 ON THE VOLUNTARY RECALL LIST FROM
 CENTRAL, PLEASE SEE WWW.SPRINKLER
 REPLACEMENT.COM.
 3) A 2 1/2 FIRE DEPARTMENT CONNECTION
 IS REQUIRED.
 4) PLEASE EXPLAIN WHY THE SPARE
 SPRINKLER HEADS WILL BE STORED IN THE
 CLUBHOUSE AS OPPOSED TO THE INDIVIDUAL
 BUILDINGS.
 5) WHAT PREVENTS THE VALVE FROM BEING
 CLOSED ON THE UNDERGROUND FIRE LINE.
  