2001-11-29 00:00:00 | 1) THE FIRE DEPARTMENT CONNECTION SHOWN | | ON THE PLANS IS NOT NEEDED AT THIS | | TIME BECAUSE IT APPEARS THAT IT WILL | | SERVE NO PURPOSE UNTIL THE FUTURE. | | 2) FIRE LINE TO BE INSTALLED IN | | ACCORDANCE WITH NFPA 24. | | 3) FIRE LINE TO BE PRESSURE TESTED | | AT 200 LBS. FOR TWO HOURS. | | 4) PLANS NEED TO BE SIGNED AND SEALED | | SINCE A TITLE BLOCK APPEARS ON THE | | PLANS. (ENGINEERING) | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|