Plan Review Notes
Plan Review Notes For Permit 01111007
Permit Number 01111007
Review Stop E
Sequence Number 3
Notes
Date Text
2002-03-13 00:00:00******************* UNSAT ************
 MODEL "E".
 1)NOTE: PLEASE NOTE OUTLET SPACING FOR
 KITCHEN COUNTERSPACE. 210-52-C-1
  
 2)NOTE: PLEASE NOTE MISSING OUTLET
 SPACING PER 210-52
  
 3)NOTE: PLEAS ENOTE THAT POOL PANEL IS
 STILL NOT SHOWN ON PANEL SCHEDULE?
 PLEASWE NOTE THAT RISER SHOWS POOL PANEL
 DISC AND POOL PANEL? PLEASE NOTE THAT
 POOL PANEL DISC IS SHOWN AT THE REAR OF
 HOUSE? AND POOL PANEL IN GARAGE?
 PLEASE CORRELATE LOCATIONS.
  
 4)NOTE: PLEASE NOTE THAT RISER SHOWS
 POOL PANEL BEING FED WITH TWO "HOTS"
 AND NO NEUTRAL AND NO EQUIPMENT GROUND-
 -ING CONDUCTOR?? SIZE PER 250-122
  
 5)NOTE: PLEASE GO OVER LOAD CALCULATIONS
 PLEASE REDO TO MEET ART220. THE 40%
 OF LOAD AFTER FIRST 10KW IS LOWER THAN
 IT SHOULD BE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372