Plan Review Notes For Permit 01111007 |
Permit Number |
01111007 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-02-13 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) MODEL "E" - 2 SETS OF PLANS REQUIRED | | FOR PLAN REVIEW. ONLY ONE SUBMITTED. | | 2) SHT A-02 BATH #2 NOT VENTED AND HORIZ | | ONTAL DRY VENT NOT ALLOWED, SEC 906.2.1 | | SEE COMMENT #1 PREVIOUS REVIEW. | | 3) SHT A-02 BATH #2 VENT PIPE SHALL RISE | | VERTICALLY OR AT AN ANGLE NOT EXCEEDING | | 45 DEG. FROM VERTICAL TO A POINT AT | | LEAST 6" ABOVE THE FLOOD RIM LEVEL. SEC | | 906.2.1 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|