Plan Review Notes
Plan Review Notes For Permit 01111007
Permit Number 01111007
Review Stop E
Sequence Number 2
Notes
Date Text
2002-02-13 00:00:00***************** UNSAT **************
 REVIEW FOR MODEL "E"
 PLEASE NOTE THAT NOT ALL ITEMS WERE
 ADDRESSED FROM FIRST REVIEW.
 PLEASE ALSO NOTE THAT OTHER CHANGES
 WERE MADE THAT NEED TO BE ADDRESSED ALSO
  
  
 1) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE NOTE THAT SOME WERE DONE ON SOME
 OF THE MODELS BUT NOT ALL.
  
 2) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 PLEASE NOTE SOME WERE DONE AND OTHERS??
 MISSING IN MANY LOCATIONS
 3)NOTE: PLEASE NOTE RECEPT IN GARAGE
 NEEDS TO BE SHOWN AS GFI PER 210-8
  
 4)NOTE: PLEASE CLARFIY OUTLET SHOWN
 UNDER WATER CLOSET?
  
 5)NOTE: PLEASE NOTE THAT OUTLET SPACING
 IN KITCHEN CHANGED?? SOME OUTLETS SHOWN
 AS DOUBLE INSTEAD? DID ADDRESS COMMENT
 FOR BEING GFI.
  
 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 FOOTER STEEL.
  
 7)NOTE: PLEASE NOTE, DERATING FOR AHU
 LOAD IS DOEN TWICE?
 PLEASE NOTE THAT LOAD CALCUALTIONS DO
 NOT MEET NEC 220.
  
 8) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 NOTE SD`S NOT TO BE WITHIN 3' OF BATHS
 AND KITCHENS. NFPA-72 2-5.2.1.6
  
 9)NOTE: PLEASE NOTE THAT RISER NOW SHOWS
 AN EQUIPMENT GROUNDING CONDUCTOR BETWEEN
 METER AND MAIN DISC. THIS IS PARALLELING
 THE NEUTRAL?
  
 10)NOTE: PLEASE NOTE THAT 30A POOL PANEL
 IS SHOWING 3/0`S FEEDING? PLEASE CLARIFY
 AND SHOW OCP ON PANEL SCHEDULE WITH
 CONDUCTOR SIZE.SHOW POOL PANEL LOCATION.
  
 11)NOTE: PLEASE NOTE THAT NOTES ON
 RIGHT STILL REFERENCE WRONG NEC FOR
 WHATS LISTED. KITCHEN NOT HAS BATH ART?
 PLEASE CORRELATE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 ***NOTE**
 ONLY ONE SET OF "E" PLANS WERE SUBMITTED
 PLEASE SUBMIT TWO FOR PERMITTING.