2002-02-13 00:00:00 | ***************** UNSAT ************** |
| REVIEW FOR MODEL "E" |
| PLEASE NOTE THAT NOT ALL ITEMS WERE |
| ADDRESSED FROM FIRST REVIEW. |
| PLEASE ALSO NOTE THAT OTHER CHANGES |
| WERE MADE THAT NEED TO BE ADDRESSED ALSO |
| |
| |
| 1) PLEASE NOTE EITHER MISSING EGRESS |
| LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| PER 210-70 OF THE NEC. |
| PLEASE NOTE THAT SOME WERE DONE ON SOME |
| OF THE MODELS BUT NOT ALL. |
| |
| 2) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52. |
| PLEASE NOTE SOME WERE DONE AND OTHERS?? |
| MISSING IN MANY LOCATIONS |
| 3)NOTE: PLEASE NOTE RECEPT IN GARAGE |
| NEEDS TO BE SHOWN AS GFI PER 210-8 |
| |
| 4)NOTE: PLEASE CLARFIY OUTLET SHOWN |
| UNDER WATER CLOSET? |
| |
| 5)NOTE: PLEASE NOTE THAT OUTLET SPACING |
| IN KITCHEN CHANGED?? SOME OUTLETS SHOWN |
| AS DOUBLE INSTEAD? DID ADDRESS COMMENT |
| FOR BEING GFI. |
| |
| 6) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| GOING TO BUILDING STEEL AND COLD WATER |
| PER 250-50. |
| FOOTER STEEL. |
| |
| 7)NOTE: PLEASE NOTE, DERATING FOR AHU |
| LOAD IS DOEN TWICE? |
| PLEASE NOTE THAT LOAD CALCUALTIONS DO |
| NOT MEET NEC 220. |
| |
| 8) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| NOTE SD`S NOT TO BE WITHIN 3' OF BATHS |
| AND KITCHENS. NFPA-72 2-5.2.1.6 |
| |
| 9)NOTE: PLEASE NOTE THAT RISER NOW SHOWS |
| AN EQUIPMENT GROUNDING CONDUCTOR BETWEEN |
| METER AND MAIN DISC. THIS IS PARALLELING |
| THE NEUTRAL? |
| |
| 10)NOTE: PLEASE NOTE THAT 30A POOL PANEL |
| IS SHOWING 3/0`S FEEDING? PLEASE CLARIFY |
| AND SHOW OCP ON PANEL SCHEDULE WITH |
| CONDUCTOR SIZE.SHOW POOL PANEL LOCATION. |
| |
| 11)NOTE: PLEASE NOTE THAT NOTES ON |
| RIGHT STILL REFERENCE WRONG NEC FOR |
| WHATS LISTED. KITCHEN NOT HAS BATH ART? |
| PLEASE CORRELATE. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |
| |
| ***NOTE** |
| ONLY ONE SET OF "E" PLANS WERE SUBMITTED |
| PLEASE SUBMIT TWO FOR PERMITTING. |