2002-03-13 00:00:00 | **************** UNSAT **************** |
| |
| MODEL "D" |
| |
| 1)NOTE: PLEASE NOTE OUTLET SPACING FOR |
| KITCHEN COUNTERSPACE PER 210-52-C1. |
| |
| 2)NOTE: PLEASE NOTE OUTLET SPACING FOR |
| WALL SPACES. 2'6'12' RULE. 210-52 |
| |
| 3)NOTE: PLEASE NOTE POOL PANEL IS STILL |
| NOT SHOWN ON MAIN PANEL SCHEUDLE? |
| PLEASE NOTE THAT RISER SHOWS POOL PANEL |
| DISC AND AND POOL PANEL? |
| PLEASE ALSO NOTE THAT PLANS SHOWS THE |
| POOL PANEL DISC AT THE REAR OF HOUSE |
| AND POOL PANEL IN GARAGE?? PLEASE |
| CORRELATE. |
| |
| 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| SHOWS POOL PANEL WITH TWO "HOTS"!, NO, |
| NEUTRAL , NO EQUIPMENT GROUNDING |
| CONDUCTOR. ??? |
| |
| 5)NOTE: PLEASE GO OVER LOAD CALCUALTIONS |
| , PLEASE REDO TO MEET 220. THE 40% OF |
| LOAD AFTER FIRST 10KW IS LOWER THAN IT |
| SHOULD BE? |
| |
| 6)NOTE: PLEASE NOTE THAT SMOKE DETECTORS |
| ARE REQUIRED INSIDE AND OUTSIDE ALL |
| BEDRROMS. PLEASE NOTE MISSING SD`S FOR |
| IN/OUT MASTER BEDROOM. NFPA-72 2-2.1.1.1 |
| |
| 7)NOTE: PLEASE NOTE MISSING EGRESS |
| LIGHTING FROM ATRIUM TO OUTSIDE.210-70 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. PLEASE CALL IF A MEETING IS |
| NEEDED. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |