2002-03-13 00:00:00**************** UNSAT ****************
  
 MODEL "D"
  
 1)NOTE: PLEASE NOTE OUTLET SPACING FOR
 KITCHEN COUNTERSPACE PER 210-52-C1.
  
 2)NOTE: PLEASE NOTE OUTLET SPACING FOR
 WALL SPACES. 2'6'12' RULE. 210-52
  
 3)NOTE: PLEASE NOTE POOL PANEL IS STILL
 NOT SHOWN ON MAIN PANEL SCHEUDLE?
 PLEASE NOTE THAT RISER SHOWS POOL PANEL
 DISC AND AND POOL PANEL?
 PLEASE ALSO NOTE THAT PLANS SHOWS THE
 POOL PANEL DISC AT THE REAR OF HOUSE
 AND POOL PANEL IN GARAGE?? PLEASE
 CORRELATE.
  
 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS POOL PANEL WITH TWO "HOTS"!, NO,
 NEUTRAL , NO EQUIPMENT GROUNDING
 CONDUCTOR. ???
  
 5)NOTE: PLEASE GO OVER LOAD CALCUALTIONS
 , PLEASE REDO TO MEET 220. THE 40% OF
 LOAD AFTER FIRST 10KW IS LOWER THAN IT
 SHOULD BE?
  
 6)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 ARE REQUIRED INSIDE AND OUTSIDE ALL
 BEDRROMS. PLEASE NOTE MISSING SD`S FOR
 IN/OUT MASTER BEDROOM. NFPA-72 2-2.1.1.1
  
 7)NOTE: PLEASE NOTE MISSING EGRESS
 LIGHTING FROM ATRIUM TO OUTSIDE.210-70
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL. PLEASE CALL IF A MEETING IS
 NEEDED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372