2002-02-13 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT A-02 BATH #2 VENT PIPE SHALL RISE
 VERTICALLY OR AT AN ANGLE NOT EXCEEDING
 45 DEG. FROM THE VERTICAL TO A POINT AT
 LEAST 6" ABOVE THE FLOOD RIM LEVEL. SEC
 906.2.1
 2) SHT A-02 RISER DIAGRAM, TUB IN BATH
 #2 NOT VENTED.
 3) SHT A-02 DISHWASHER NOT TRAPPED. IT
 SHALL DRAIN INTO THE GARBAGE DISPOSAL OR
 THE SINK TAILPIECE. SHOW THIS BOTH ON
 THE RISER DIAGRAM AND FLOOR PLAN.
 4) SHT A-02 VENT FOR SHOWER IN M/BATH
 CAN NOT COME OUT OF THE BOTTOM OF SHOWER
 AS SHOWN ON FLOOR PLAN. SEE COMMENT #3
 FROM PREVIOUS PLAN REVIEW.
  