Plan Review Notes For Permit 01111006 |
Permit Number |
01111006 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-02-13 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) SHT A-02 BATH #2 VENT PIPE SHALL RISE | | VERTICALLY OR AT AN ANGLE NOT EXCEEDING | | 45 DEG. FROM THE VERTICAL TO A POINT AT | | LEAST 6" ABOVE THE FLOOD RIM LEVEL. SEC | | 906.2.1 | | 2) SHT A-02 RISER DIAGRAM, TUB IN BATH | | #2 NOT VENTED. | | 3) SHT A-02 DISHWASHER NOT TRAPPED. IT | | SHALL DRAIN INTO THE GARBAGE DISPOSAL OR | | THE SINK TAILPIECE. SHOW THIS BOTH ON | | THE RISER DIAGRAM AND FLOOR PLAN. | | 4) SHT A-02 VENT FOR SHOWER IN M/BATH | | CAN NOT COME OUT OF THE BOTTOM OF SHOWER | | AS SHOWN ON FLOOR PLAN. SEE COMMENT #3 | | FROM PREVIOUS PLAN REVIEW. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|