2002-02-13 00:00:00 | ***************** UNSAT *************** |
| REVIEW FOR MODEL "D" |
| PLEASE NOTE THAT NOT ALL NOTES FROM |
| FIRST REVIEW WERE ADDRESSED AND THEN |
| OTHER CHANGES WERE MADE. |
| |
| 1) PLEASE NOTE EITHER MISSING EGRESS |
| LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| PER 210-70 OF THE NEC. |
| PLEASE NOTE THAT SOME LOCATIONS WERE |
| DONE AND OTHER NOT? |
| |
| 2) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| TO MEET 2`,6`,12` RULE PER 210-52. |
| PLEASE NOTE STILL MISSING IN LOCATIONS |
| |
| |
| 3)NOTE: PLEASE NOTE AS CHANGES WERE |
| MADE TO SHOW KITCHEN COUNTERTOPAS |
| GFI`S, LOCATION WERE MOVED AND NOW DO |
| NOT MEET 210-52-C1 PLEASE ALSO NOTE |
| ISLAND REQ`S ADDITIONAL PER 210-52-C3 |
| ` |
| 4)NOTE: PLEASE NOTE THAT ALL OTHER |
| MODELS SHOW AN ATTIC ACCESS IN GARAGE |
| OR OTHER? PLEASE NOTE 210-70 IF THIS |
| MODEL ACCESS. |
| |
| 5)NOTE: PLEASE NOTE THAT NOTES ON RIGHT |
| STILL SHOW WRONG CODE REFERENCE FOR |
| KITCHEN. SHOWS ART FOR BATHS? |
| |
| 6)NOTE: PLEASE NOTE, LOAD CALCULATIONS |
| NEED TO MEET 220. DERATING IS DONE |
| TWICE FOR AHU LOAD. AND FINAL KW RATING |
| IS DIVIDED BY 120VOLTS ON A 230/240 V |
| SERVICE. PLEASE CORRECT. |
| |
| 7) NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| GOING TO BUILDING STEEL AND COLD WATER |
| PER 250-50. |
| |
| 8)NOTE: PLEASE NOTE THAT PLANS NOW SHOW |
| AN EQUIPMENT GROUNDING CONDUCTOR BETWEEN |
| FIRST MEANS OF DISC AND MAIN? PLEASE |
| NOTE THAT THIS IS PARALLELING THE |
| NEUTRAL? |
| |
| 9)NOTE: PLEASE NOTE THAT RISER SHOWS |
| 3/0`S GOING TO 30 POOL PANEL? |
| PLEASE SHOW OCP AND WIRE SIZE FOR POOL |
| PANEL. PLEASE SHOW PANEL LOCATION ON |
| PLANS. |
| |
| 10)NOTE: PLEASE NOTE RECEPT ON GARAGE |
| NEEDS TO GFI PER 210-8. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |