Plan Review Notes
Plan Review Notes For Permit 01111006
Permit Number 01111006
Review Stop E
Sequence Number 2
Notes
Date Text
2002-02-13 00:00:00***************** UNSAT ***************
 REVIEW FOR MODEL "D"
 PLEASE NOTE THAT NOT ALL NOTES FROM
 FIRST REVIEW WERE ADDRESSED AND THEN
 OTHER CHANGES WERE MADE.
  
 1) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE NOTE THAT SOME LOCATIONS WERE
 DONE AND OTHER NOT?
  
 2) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 PLEASE NOTE STILL MISSING IN LOCATIONS
  
  
 3)NOTE: PLEASE NOTE AS CHANGES WERE
 MADE TO SHOW KITCHEN COUNTERTOPAS
 GFI`S, LOCATION WERE MOVED AND NOW DO
 NOT MEET 210-52-C1 PLEASE ALSO NOTE
 ISLAND REQ`S ADDITIONAL PER 210-52-C3
 `
 4)NOTE: PLEASE NOTE THAT ALL OTHER
 MODELS SHOW AN ATTIC ACCESS IN GARAGE
 OR OTHER? PLEASE NOTE 210-70 IF THIS
 MODEL ACCESS.
  
 5)NOTE: PLEASE NOTE THAT NOTES ON RIGHT
 STILL SHOW WRONG CODE REFERENCE FOR
 KITCHEN. SHOWS ART FOR BATHS?
  
 6)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 NEED TO MEET 220. DERATING IS DONE
 TWICE FOR AHU LOAD. AND FINAL KW RATING
 IS DIVIDED BY 120VOLTS ON A 230/240 V
 SERVICE. PLEASE CORRECT.
  
 7) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
  
 8)NOTE: PLEASE NOTE THAT PLANS NOW SHOW
 AN EQUIPMENT GROUNDING CONDUCTOR BETWEEN
 FIRST MEANS OF DISC AND MAIN? PLEASE
 NOTE THAT THIS IS PARALLELING THE
 NEUTRAL?
  
 9)NOTE: PLEASE NOTE THAT RISER SHOWS
 3/0`S GOING TO 30 POOL PANEL?
 PLEASE SHOW OCP AND WIRE SIZE FOR POOL
 PANEL. PLEASE SHOW PANEL LOCATION ON
 PLANS.
  
 10)NOTE: PLEASE NOTE RECEPT ON GARAGE
 NEEDS TO GFI PER 210-8.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372