Plan Review Notes For Permit 01111006 |
Permit Number |
01111006 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-01-15 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | SBC = STANDARD BUILDING CODE | | SBC*= STANDARD BUILD'G CODE (AMENDMENTS) | | | | 1) SEE REVIEWS, DATED 1/15/02, OF | | MODELS B AND C (PERMIT NOS 01111002 AND | | 01111005) FOR GENERAL COMMENTS. COMMENTS | | SPECIFIC TO MODEL D ARE LISTED BELOW. | | | | 2) SBC 705.1.3OPENING PROTECTIVES. | | TABLE 600 REQUIRES THE GLASS BLOCK | | WINDOW TO THE 'NOOK' ON THE COMMON | | PROPERTY (ZERO LOT) LINE TO HAVE A FIRE | | RESISTANCE RATING OF ONE HOUR. | | | | 3) SHEET A-03, FLOOR PLAN.THE BED 2 | | DOOR TO THE ATRIUM IS SHOWN AS REF 21. | | THERE IS NO REFERENCE 21 SHOWN ON THE | | DOOR SCHEDULE.THE 2'-6" FRENCH DOOR | | SHOWN AT THE END OF THE SCHEDULE IS | | SHOWN AS TYPE I, AS ARE THE BI-FOLD | | DOORS.AMEND THE SCHEDULE TO GIVE | | CORRECT DOOR REF MARKS AND DOOR TYPES. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|