2001-12-20 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT SEPARATE PLANS
 NEED TO BE SUBMITTED FOR EACH SFR.
  
 2)NOTE: PLEASE NOTE LOAD SHOWN FOR MAIN
 PANEL IS SHOWN ABOVE 200AMPS.
  
 3)NOTE: PLEASE NOTE OCP FOR WATER HEATER
 NEEDS TO BE AT 125% PER 422-13.
 PLEASE CORRELATE OCP WITH WIRE SIZE.
  
 4)NOTE: PLEASE NOTE MISSING EGRESS LIGHT
 -ING IN MANY LOCATIONS, SOME AREAS SHOWN
 WITH OPT LTS WHERE LTS ARE REQ`D 210-70
 HALLS, OUTSIDE ETC.
  
 5)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C COND UNIT. 309-2 MECH CODE.
  
 6)NOTE: PLEASE NOTE THAT PLANS NEED TO S
 SHOW MAIN DICSA NEXT TO METER AS SHOWN
 ON RISER DIAGRAM.
  
 7) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 PLEASE NOTE THAT NOTES NEED TO SHOW THE
 CORRECT ART # IF SHOWN. SHOWN AS 210-52D
 WHICH OS FOR BATHS?
  
 8)NOTE:PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 PLEASE NOTE PLANS SHOW 210-52D AND
 AND COMES FROM 210-11-C-3
 AS LONG AS THIS IS LISTED ON PANEL
 SCHEUDULE THEN NOT REQ`D ON NOTES.
  
 9)NOTE: PLEASE CLARIFY MISSING EQUIPMENT
 GROUNDING COND PER 2505-122 FROM POOL
 PANEL TO MAIN PANEL.
  
 10)NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR]
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372