2002-03-13 00:00:00************** UNSAT *****************
 MODEL "C".
 1) NOTE: PLEASE NOTE THAT OUTLET SPACING
 NEEDS TO MEET 210-52. 2` AND 6` RULE.
  
 2)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO BE GONE OVER. PLEASE NOTE THAT
 AFTER THE FIRST 10KW WASA TAKEN, 40%
 OF REMAINING, SEEMS TO HAVE COME OUT
 TOO LOW.
 PLEASE ADJUST.
  
 3)NOTE: PLEASE NOTE POOL PANEL IS STILL
 NOT LISTED ON MAIN PANEL SCHEDULE??
 PLEASE NOTE THAT RISER SHOWS A POOL
 PANEL DISC AND POOL PANEL?
 PLEASE ALSO NOTE THAT POOL PANEL IS IN
 GARAGE AND POOL PANEL DISC IS SHOWN AT
 THE REAR OF HOUSE?? PLEASE CORRELATE.
  
 4)NOTE: PLEASE NOTE FEED TO POOL PANEL
 SHOWING TWO "HOTS"? NO NEUTRAL, NO
 EQUIPMENT GROUNDING CONDUCTOR??
 PLEASE CORRECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS.
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372