2002-02-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/15/02:
  
 1) SEE REVIEW, DATED 2/14/02, OF MODEL B
 (PERMIT NO. 01111002) FOR GENERAL
 COMMENTS.COMMENTS SPECIFIC TO MODEL C
 ARE LISTED BELOW.
  
 4) THIS COMMENT HAS NOT BEEN ADDRESSED.
 PART OF THE SECOND FLOOR BED 3 EXTERIOR
 WALL FACES THE COMMON PROPERTY LINE AT A
 DISTANCE OF 6'-8".FROM TABLE 600, THAT
 PART OF THE WALL IS REQUIRED TO HAVE A
 FIRE RESISTANCE RATING OF ONE HOUR.
 SUBMIT DETAILS TO SHOW THE RATING OF
 THIS WALL.
  
 5) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE MODEL D DOOR SCHEDULE IS
 STILL MISSING ALL REFERENCE MARKS ABOVE
 NO. 14
  
 6) THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.SHEET A-07 REFERS TO BEAM
 REF. 8F801B BUT THIS REF. DOES NOT MATCH
 THAT SHOWN ON BEAM SCHEDULE (SHEET A-06)
 AMEND THE BEAM REFERENCE TO SUIT THAT
 GIVEN ON THE SCHEDULE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS