2002-02-15 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 1/15/02: |
| |
| 1) SEE REVIEW, DATED 2/14/02, OF MODEL B |
| (PERMIT NO. 01111002) FOR GENERAL |
| COMMENTS.COMMENTS SPECIFIC TO MODEL C |
| ARE LISTED BELOW. |
| |
| 4) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| PART OF THE SECOND FLOOR BED 3 EXTERIOR |
| WALL FACES THE COMMON PROPERTY LINE AT A |
| DISTANCE OF 6'-8".FROM TABLE 600, THAT |
| PART OF THE WALL IS REQUIRED TO HAVE A |
| FIRE RESISTANCE RATING OF ONE HOUR. |
| SUBMIT DETAILS TO SHOW THE RATING OF |
| THIS WALL. |
| |
| 5) THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED.THE MODEL D DOOR SCHEDULE IS |
| STILL MISSING ALL REFERENCE MARKS ABOVE |
| NO. 14 |
| |
| 6) THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED.SHEET A-07 REFERS TO BEAM |
| REF. 8F801B BUT THIS REF. DOES NOT MATCH |
| THAT SHOWN ON BEAM SCHEDULE (SHEET A-06) |
| AMEND THE BEAM REFERENCE TO SUIT THAT |
| GIVEN ON THE SCHEDULE. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |